GENERAL NOTES for configuration.

FUNC = This will memorize the new value of the selected parameter and go to the next parameter (increasing order).

MAN = This will scroll back the parameters without memorization of the new value.

s= This will increase the value of the selected parameter

t= This will decrease the value of the selected parameter.

CONFIGURATION PROCEDURE

1)Remove the instrument from its case.

2)Set the dip switch V101to the open condition (see fig. 13).

3)Re-insert the instrument.

4)Switch on the instrument.

The display will show COnF.

NOTE : If "CAL" indication is displayed, press immediately the s pushbutton and return to the configuration procedure.

5) Push the FUNC pushbutton.

SEr1 = Serial interface protocol

OFF

= No serial interface

Ero

= Polling/selecting ERO

nbUS

= Modbus

jbUS

= Jbus

SEr2 = Serial link device address Not available when SEr1 = OFF From 1 to 95 for ERO protocol.

From 1 to 255 for all the other protocols.

NOTE: the electrical characteristic of the RS 485 serial interface allows you the connection of 31 devices maximum.

SEr3 = Baude rate for serial link

Not available when SEr1 = OFF From 600 to 19200 baud.

NOTE: 19200 baud is shown on display as 19.2.

SEr4 = Byte format for serial link

Not available when SEr1 = OFF

7E = 7 bits + even parity (For ERO protocol only) 7O = 7 bits + odd parity (For ERO protocol only) 8E = 8 bits + even parity

8O = 8 bits + odd parity

8 = 8 bits no parity

P1 - Input type and standard range

 

 

 

0

= TC type

L

range

0

/ +400.0 °C

1

= TC type

L

range

0

/

+900

°C

2

= TC type

J

range-100.0

/ +400.0 °C

3

= TC type

J

range

-100

/

+1000

°C

4

= TC type

K

range-100.0

/ +400.0 °C

5

= TC type

K

range

-100

/

+1370

°C

6

= TC Type

T

range-199.9

/ +400.0 °C

7

= TC type

N

range

-100

/

+1400

°C

8

= TC type

R

range

0

/

+1760

°C

9

= TC type

S

range

0

/

+1760

°C

10

= RTD type Pt 100

range-199.9

/ +400.0 °C

11

= RTD type Pt 100

range

-200

/

+800

°C

12

= mV

Linear

range

0

/

60 mV

13

= mV

Linear

range

12

/

60 mV

14

= mA

Linear

range

0

/

20 mA

15

= mA

Linear

range

4

/

20 mA

16

= V

Linear

range

0

/

5 V

17

= V

Linear

range

1

/

5 V

18

= V

Linear

range

0

/

10 V

19

= V

Linear

range

2

/

10 V

20

= TC type

L

range

0

/

+1650 °F

10

1604-7-1-AB.p65

10

5/16/00, 10:50 AM

Page 13
Image 13
Chromalox 1604-7 user manual SEr1 = Serial interface protocol, Off, SEr3 = Baude rate for serial link