ERROR LIST
SEr Serial interface parameter error.
100 Write EEPROM error.
150 CPU error.
200 Tentative to write on protected
memory.
201 - 2xx Configuration parameter error. The
two less significant digits shown the
number of the wrong parameter (ex.
209 Err shows an Error on P9
parameter)
299 Error on control output selection.
301 Selected input calibration error
307 RJ input calibration error
320 Analog retransmission calibration
error.
400 Control parameters error
500 Auto-zero error
502 RJ error
510 Error during calibration procedure.
NOTES
1) When a configuration parameter error is
detected, it is sufficient to repeat the configura-
tion procedure of the specified parameter.
2) If error 400 is detected, push contemporarily
the t and s pushbuttons for loading the
default parameters then repeat control
parameter setting.
3) For all the other errors, contact your supplier.