MOUNTING REQUIREMENTS

Select a mounting location where there is

 

minimum vibration and the ambient temperature

 

range between 0 and 50 °C.

 

The instrument can be mounted on a panel up to

 

15 mm thick with a square cutout of 45 x 45 mm.

 

For outline and cutout dimensions refer to Fig. 2.

 

The surface texture of the panel must be better

 

than 6,3 mm.

 

The instrument is shipped with rubber panel

 

gasket (50 to 60 Sh).

 

To assure the IP65 and NEMA 4 protection, insert

 

the panel gasket between the instrument and the

 

panel as shown in fig. 1.

Screw

While holding the instrument against the panel

 

proceed as follows:

 

1) insert the gasket in the instrument case;

bracket

2) insert the instrument in the panel cutout;

Panel

3) pushing the instrument against the panel,

 

insert the mounting bracket;

 

4)with a screwdriver, turn the screws with a torque between 0.3 and 0.4 Nm.

Gasket

Fig. 1

1

1604-7-1-AB.p65

1

5/16/00, 10:50 AM