Grd1 Ramp applied to an increasing set point change

Range: from 1 to 100 digits per minute. Above this value the display shows “InF” meaning that the transfer will be done as a step change.

Grd2 Ramp applied to a decreasing set point changes

For other details see Grd1 parameter. OLH Output high limit

Range:

-From 0.0 to 100.0 % of the output span when device is configured with one control output.

-From -100.0 to 100.0% of the output span when device is configured with two control outputs.

tOL Time duration of the output power limiter (soft start)

Range: from 1 to 540 min. Above this value the display shows “InF” meaning that the limiting action is always on. Note: The tOL can be modified but the new value will become operative only at the next instrument start up.

rnP Control output max. rate of rise This parameter is available only when Pb is different from zero or one control output is a linear output type.

Range: From 0.1 % to 25.0 % of the output span/second. Above this value the display shows “InF” meaning that no limit is imposed.

Note:the rnP parameter is active on a linear control output even if the device is in ON/OFF control mode.