A-3
Cisco ONS 15454 SDH Reference Manual, R5.0
April 2008
AppendixA Hardware Spec ifications
A.1.8 System Timing

A.1.8 System Timing

The ONS 15454 SDH has the following system timing specifications:
Stratum 3E, per ITU-T G.813
Free running accuracy: +/– 4.6 ppm
Holdover stability: 3.7 exp –7/day, including temperature (< 255 slips in first 24 hours)
Reference: External building integrate d timing supply (BITS), line, internal

A.1.9 System Power

The ONS 15454 SDH has the following power specifications:
Input voltage: –48 VDC
Power consumption: Configuration dependent, 53 W for fan tray; 650 W (maximum draw w/cards)
Power requirements:
Nominal: –48 VDC
Tolerance limits: –40.5 to –57.0 VDC
Power terminals: 3WK3 Combo-D power cable connector (MIC-A/P and MIC-C/T/P faceplates)
Fusing: 100 A fuse panel; minimum 30 A fuse per shelf

A.1.10 System Environmental Specifications

The ONS 15454SDH has the following environmental specifications:
Operating temperature: 0 to +40 degrees Celsius (32 to 104 degrees Fahrenheit)
Operating humidity: 5 to 95%, noncondensing

A.1.11 Dimensions

The ONS 15454 SDH shelf assembly has the following dimensions:
Height: 616.5 mm (24.27 in.)
Width: 535 mm (17 in.) without mounting ears attached
Depth: 280 mm (11.02 in.)
Weight: 26 kg empty (57.3 lb)
A.2 SFP Specifications
Table A -1 lists the specifications for the available Small Form-factor Pluggables (SFPs).