10. COOLING CYCLE HEAVY REPAIR
Process | Contents | Tools | |
Remove | * Cut charging pipe ends (Comp. & Dryer) and |
| |
refrigerant | * Nipper, side cutters | ||
discharge refrigerant from drier and compressor. | |||
Residuals |
| ||
|
| ||
|
|
| |
| * Confirm refrigerant |
| |
Parts | compressor and drier. |
| |
* Confirm N2 sealing and packing conditions before use. | * Pipe Cutter, Gas welder, | ||
replacement | |||
Use good one for welding and assembly. | N2 gas | ||
and welding | |||
* Weld under nitrogen gas atmosphere. |
| ||
|
| ||
| * Repair in a clean and dry place. |
| |
|
|
| |
| * Evacuate for more than forty minutes after connecting | * Vacuum pump | |
Vacuum | manifold gauge hose and vacuum pump to high (drier) | ||
, Manifold gauge. | |||
| and low (compressor) pressure sides. | ||
|
| ||
|
|
| |
Refrigerant | * Weigh and control the bombe in a vacuum conditions | * Bombe (mass cylinder), | |
with electronic scales and charge through compressor | |||
charging and | refrigerant manifold gauge, | ||
inlet (Process tube). | |||
charging | electronic scales, punching | ||
* Charge while refrigerator operates). | |||
inlet welding | off flier, gas welding machine | ||
* Weld carefully after inlet pinching. | |||
|
| ||
|
|
| |
| * Check leak at weld joints. |
| |
Check | Note :Do not use soapy water for check. |
| |
* Check cooling capacity | * Electronic Leak Detector, | ||
refrigerant leak | |||
and cooling | → Check condenser manually to see if warm. | Driver. | |
→ Check hot pipe manually to see if warm. | |||
capacity |
| ||
→ Check frost formation on the whole surface of the |
| ||
|
| ||
| evaporator. |
| |
|
|
| |
Compressor | * Remove flux from the silver weld joints with soft |
| |
brusher wet rag. (Flux may be the cause of corrosion |
| ||
compartment |
| ||
and leaks.) | * Copper brush, Rag, Tool box | ||
and tools | |||
*Clean tools and store them in a clean tool box |
| ||
arrangement |
| ||
or in their place. |
| ||
|
| ||
|
|
| |
Transportation | * Installation should be conducted in accordance with |
| |
the standard installation procedure. (Leave space of |
| ||
and |
| ||
more than 5 cm from the wall for compressor |
| ||
installation |
| ||
compartment cooling fan mounted model.) |
| ||
|
| ||
|
|
|
72