Delta DT3 instruction sheet Alarm Outputs, Al-H

Models: DT3

1 21
Download 21 pages 52.54 Kb
Page 16
Image 16

screen

. If the password is incorrect, the screen will return to PV/SV display mode.

3.Enter the new password two times in the screen. The screen will return to PV/SV display mode with the keys unlocked. If the two entries of password are not the same, the screen will go back to the state of step 2.

¾Cannot remember the password:

Restore factory settings to release the locking.

Alarm Outputs

Two alarm outputs are provided in the machine, a maximum of 3 alarm outputs can be expanded. A total of 19 Independent alarm settings can be made as listed in the table. Additional settings are provided, such as alarm delay, alarm standby, alarm output hold, alarm reverse output, and alarm peak record, as described as follows:

aAlarm Delay Setting: Sets alarm delay time. When the movement conforms to the alarm setting mode, controller will delay the generation of an alarm signal; an alarm will only be activated when the alarm conditions remains confirmed within the delayed period of time.

bAlarm Standby Setting: An alarm detection will only be activated when the measured value falls within the ±5 range of the specified input value, so as to prevent an alarm activation on the start-up if the condition conforms to the alarm setting.

cAlarm Output Hold Setting: The alarm message will be held when the alarm activates, unless the control switches off the alarm.

dAlarm Reverse Output Setting: An alarm output can be set for NC( Normal close) or NO(Normal Open).

eAlarm Peak Record Setting: For recording the peak value of the alarm signal.

 

Set

 

Alarm Type

 

 

 

 

 

 

 

 

 

Alarm Output Operation

 

 

Value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

Alarm function disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

Deviation upper- and lower-limit:

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates when PV value is higher than the setting value SV+(AL-H)

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or lower than the setting value SV-(AL-L).

 

SV-(AL-L)

SV

SV+(AL-H)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

Deviation upper-limit:

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates when PV value is higher than the setting value SV+(AL-H).

 

 

 

 

 

 

 

SV

SV+(AL-H)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

Deviation lower-limit:

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates when PV value is lower than the setting value SV-(AL-L).

 

 

 

 

 

 

SV

 

 

 

 

 

 

 

 

 

 

 

SV-(AL-L)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

Absolute value upper- and lower-limit:

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates when PV value is higher than the setting value AL-H or

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lower than the setting value AL-L.

 

 

 

 

 

 

 

 

AL-L

 

 

 

 

AL-H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

Absolute value upper-limit:

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates when PV value is higher than the setting value AL-H.

 

 

 

 

 

 

 

 

 

 

AL-H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

Absolute value lower-limit:

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates when PV value is lower than the setting value AL-L.

 

 

AL-L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

Hysteresis upper-limit alarm output:

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates if PV value is higher than the setting value SV+(AL-H). This

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

alarm output is OFF when PV value is lower than the setting value SV+(AL-L).

 

 

 

 

 

 

 

 

 

 

 

 

AL-L

AL-H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

Hysteresis lower-limit alarm output:

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This alarm output operates if PV value is lower than the setting value SV-(AL-H). This

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

alarm output is OFF when PV value is higher than the setting value SV-(AL-L).

 

 

 

 

 

 

 

 

AL-H

AL-L

 

 

 

 

 

9Disconnection Alarm: This alarm output operates if the sensor connection is incorrect or has been disconnected.

10

Time Counter Alarm

 

 

 

 

 

 

 

11

CT1 Alarm: CT1 is ON if the value of CT1 is lower than the value of AL-L or higher than

ON

 

 

 

 

 

AL-H.

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

12

CT2 Alarm: CT2 is ON if the value of CT2 is lower than the value of AL-L or higher than

 

AL-L

AL-H

 

 

AL-H.

 

 

 

 

 

 

 

 

 

 

13When SOAK status (temperature hold) happens to PID program control, alarm output is ON.

14When RAMP UP status happens to PID program control, alarm output is ON.

15When RAMP DOWN status happens to PID program control, alarm output is ON.

16When RUN status happens to PID program control, alarm output is ON.

16

Page 16
Image 16
Delta DT3 instruction sheet Alarm Outputs, Al-H