Auto Fine-tune the PID value. During the calculation, AT LED lights up in the display panel. When the PV value generates 2 curves of temperature oscillation based on the SV value, the AT process is completed and the AT LED in the panel goes out. The calculated PID

parameters are displayed in , , , and , of which their content can be revised by the user.

¾Automatic switching-over Multiple PID sets:

Set parameter to 0 (PID 0, the first set) inRegulation Mode, set the required SV value (e.g. 100 degree), set parameter as ON; on completion of auto fine-tuning, the system fills in parameters =100, , , and automatically, their content can be revised by the user.

Set parameter to 1 (PID 1, the second set), set the required SV value (e.g. 150 degree), set parameter as ON; on

completion of auto fine-tuning, the system fills in parameters =150, , , and automatically.

Set parameter to AUTO, System will verify on its own whether the current SV value is closer to parameter or ,

and load the corresponding PID set automatically. E.g., if SV=110, system will load parameters. If SV=140, system will load parameters.

If more SV groups are required, PID2~PID5 can be set up with the same sequence as described above.

Tune Function

This machine provides 2 tuning methods (Auto_Tuning and Self_Tuning) for automatic generation of PID parameters (only applicable when control mode is set to PID control).

zAuto_Tuning: by full output of heating or cooling, temperature is allowed to oscillate up and down. Attain parameters of the magnitude and period, calculate P, I, D, IOF parameters; in addition, save the temperature setting value for performing AT, for the use of PID control. After Auto_Tuning, PID control will be carried out automatically.

¾Set parameter to in Initial Setting Mode

¾AT setting: Set parameter to in Regulation Mode

zSelf_Tuning: By full output of heating or cooling, max. slope of temperature alteration and system delay can be attained from the Temperature-Time Curve, and P, I, D, IOF parameters can be calculated. Self tuning can be carried out in RUN mode and in STOP mode. In the RUN mode, PID parameters are allowed to be updated when the machine is running; in the STOP mode, PID parameters for the SV value can be attained.

¾Set parameter to inInitial Setting Mode

¾ST Setting: set parameter to in Regulation Mode

Set Reverse Output

¾output 1 reverse setting: Set a value corresponding to Y position by parameter in Initial Setting Mode, such as xxxY (Y

can be 0 or 1; 0: forward; 1: reverse)

¾output 2 reverse setting: Set a value corresponding to Y position by parameter in Initial Setting Mode, such as xxYx (Y

can be 0 or 1; 0: forward; 1: reverse)

Limits controlling the output range

Maximum and minimum output can be limited; if the original maximum control output is 100% and the minimum control output is 0%, you may set the maximum control output to 80% and the minimum control output to 20%.

¾Setting the upper limit of control output: Set values for parameters (output 1), (output 2) inOperation Mode.

¾Setting the lower limit of control output: Set values for parameters (output 1), (output 2) inOperation Mode.

CT Function

This controller provides maximum 2 CTs (CT1 and CT2) for measuring current values of output 1 and output 2; when the corresponding output is ON, use CT to measure the corresponding current. An alarm will be activated (ON) when the current exceeds the setting range of alarm. (A hardware PCB is required.)

¾Insert CT1, CT2 PCBs to Option1, Option2

¾Set the corresponding alarm to CT Alarm: Please refer to “Alarm Output Setting”.

¾Set the upper limit of CT alarm output (unit: 0.1A): Please refer to “Alarm Output Setting”.

¾Set the lower limit of CT alarm output (unit: 0.1A): Please refer to “Alarm Output Setting”.

¾ Read current values of CT1, CT2: Read current values by parameters

,

in Operation Mode.

13

Page 13
Image 13
Delta DT3 instruction sheet Tune Function, Set Reverse Output, Limits controlling the output range, CT Function