17When HOLD status happens to PID program control, alarm output is ON.
18When STOP status happens to PID program control, alarm output is ON.
19When END status happens to PID program control, alarm output is ON.
¾To set Alarm Mode: Use the parameters , , in 【Initial Setting Mode】 to select the alarm mode. There are in total of 19 different modes (as listed in the table above).
¾To set Deviation Upper Limit of Alarm: Use the parameters , , in 【Operation Mode】to set the deviation upper limit.
¾To set Deviation Lower Limit of Alarm: Use the parameters , , in 【Operation Mode】 to set the deviation lower limit.
¾To set Alarm Delay Time(Unit: seconds): Use the parameters , , in 【Initial Setting Mode】 to set the alarm delay time.
¾To set Reverse Alarm: Use the parameters , , in【Initial Setting Mode】 to set the digit Y of value xxYx
(When Y=0: reverse, Y=1: forward)
¾To set Alarm 3: Alarm 3 function is available when an output board is connected to Output 2. Use the parameter in【Initial
Setting Mode】, press the key ▲ or ▼ to select for the following control output items: H1H2, C1H2… H1A2(H defines heating, C defines cooling, 1 indicates Output1, 2 indicates Output2 , A indicates Alarm3).
¾Select x1A2( set x to H or C) to operates Alarm3. To set Standby Alarm: Use the parameters , , in 【Initial
Setting Mode】 to set the digit Y of value xxxY (When Y=0: normal opeartion, Y=1: standby).
¾To set Hold Alarm: Use the parameters , , in【Initial Setting Mode】 to set the digit Y of value xYxx ( When
Y=0: normal operation, Y=1: Hold).
¾ To set Peak Alarm Signal: Use the parameters | , | , | in【Initial Setting Mode】 to set the digit Y of value Yxxx | |||
(when Y=0: normal operation, Y=1: peak signal). |
|
|
| |||
Note: Refer to the table |
|
|
|
|
| |
Bit3 | Bit2 | Bit1 |
| Bit0 |
|
|
Peak Alarm | Hold Alarm | Reverse Alarm | Standby Alarm |
|
|
¾PV Color Change Function: This controller provides PV color change function. The PV display color will be changed if the selected
alarm energized. Use the parameter (PV color) in【Initial Setting Mode】 to select the alarm, selectable items are , , , and .
RS-485 Communication
1.Supporting transmission speed: 2,400, 4,800, 9,600, 19,200, 38,400bps
2.
3.Communication protocol: Modbus (ASCII or RTU)
4.Function code: 03H to read the contents of register (Max. 8 words). 06H to write 1 (one) word into register. 02H to read the bits data (Max.16 bits). 05H to write 1 (one) bit into register.
5.Address and Content of Data Register:
Address | Content |
| Definition |
|
| Measuring unit is 0.1, updated one time in 0.1 second | |
|
| The following reading value display indicates error occurs: | |
|
| 8002H | : Initial process (Temperature value is not got yet) |
1000H | Present value (PV) | 8003H | : Temperature sensor is not connected |
|
| 8004H | : Temperature sensor input error |
|
| 8006H | : Cannot get temperature value, ADC input error |
|
| 8007H | : Memory read/write error |
|
|
| |
1001H | Set point (SV) | Unit is 0.1, oC or oF | |
|
|
| |
1002H | The data content should not be higher than the temperature range | ||
1003H | The data content should not be lower than the temperature range | ||
|
|
| |
1004H | Input temperature sensor type | Please refer to the contents of the “Temperature Sensor Type and Temperature | |
| Range” for detail | ||
|
| ||
1005H | Control method | 0: PID, 1: ON/OFF, 2: manual tuning, 3: FUZZY | |
|
|
|
|
17