Delta DT3 instruction sheet RS-485 Communication

Models: DT3

1 21
Download 21 pages 52.54 Kb
Page 17
Image 17

17When HOLD status happens to PID program control, alarm output is ON.

18When STOP status happens to PID program control, alarm output is ON.

19When END status happens to PID program control, alarm output is ON.

¾To set Alarm Mode: Use the parameters , , in Initial Setting Modeto select the alarm mode. There are in total of 19 different modes (as listed in the table above).

¾To set Deviation Upper Limit of Alarm: Use the parameters , , in Operation Modeto set the deviation upper limit.

¾To set Deviation Lower Limit of Alarm: Use the parameters , , in Operation Modeto set the deviation lower limit.

¾To set Alarm Delay Time(Unit: seconds): Use the parameters , , in Initial Setting Modeto set the alarm delay time.

¾To set Reverse Alarm: Use the parameters , , inInitial Setting Modeto set the digit Y of value xxYx

(When Y=0: reverse, Y=1: forward)

¾To set Alarm 3: Alarm 3 function is available when an output board is connected to Output 2. Use the parameter inInitial

Setting Mode, press the key ▲ or ▼ to select for the following control output items: H1H2, C1H2… H1A2(H defines heating, C defines cooling, 1 indicates Output1, 2 indicates Output2 , A indicates Alarm3).

¾Select x1A2( set x to H or C) to operates Alarm3. To set Standby Alarm: Use the parameters , , in Initial

Setting Modeto set the digit Y of value xxxY (When Y=0: normal opeartion, Y=1: standby).

¾To set Hold Alarm: Use the parameters , , inInitial Setting Modeto set the digit Y of value xYxx ( When

Y=0: normal operation, Y=1: Hold).

¾ To set Peak Alarm Signal: Use the parameters

,

,

inInitial Setting Modeto set the digit Y of value Yxxx

(when Y=0: normal operation, Y=1: peak signal).

 

 

 

Note: Refer to the table

 

 

 

 

 

Bit3

Bit2

Bit1

 

Bit0

 

 

Peak Alarm

Hold Alarm

Reverse Alarm

Standby Alarm

 

 

¾PV Color Change Function: This controller provides PV color change function. The PV display color will be changed if the selected

alarm energized. Use the parameter (PV color) inInitial Setting Modeto select the alarm, selectable items are , , , and .

RS-485 Communication

1.Supporting transmission speed: 2,400, 4,800, 9,600, 19,200, 38,400bps

2.Non-supported formats: 7, N, 1 or 8, O, 2 or 8, E, 2

3.Communication protocol: Modbus (ASCII or RTU)

4.Function code: 03H to read the contents of register (Max. 8 words). 06H to write 1 (one) word into register. 02H to read the bits data (Max.16 bits). 05H to write 1 (one) bit into register.

5.Address and Content of Data Register:

Address

Content

 

Definition

 

 

Measuring unit is 0.1, updated one time in 0.1 second

 

 

The following reading value display indicates error occurs:

 

 

8002H

: Initial process (Temperature value is not got yet)

1000H

Present value (PV)

8003H

: Temperature sensor is not connected

 

 

8004H

: Temperature sensor input error

 

 

8006H

: Cannot get temperature value, ADC input error

 

 

8007H

: Memory read/write error

 

 

 

1001H

Set point (SV)

Unit is 0.1, oC or oF

 

 

 

1002H

Upper-limit of temperature range

The data content should not be higher than the temperature range

1003H

Lower-limit of temperature range

The data content should not be lower than the temperature range

 

 

 

1004H

Input temperature sensor type

Please refer to the contents of the “Temperature Sensor Type and Temperature

 

Range” for detail

 

 

1005H

Control method

0: PID, 1: ON/OFF, 2: manual tuning, 3: FUZZY

 

 

 

 

17

Page 17
Image 17
Delta DT3 instruction sheet RS-485 Communication