1006H | Heating/Cooling control selection | Refer to Ouputput Mode Selection | |
|
|
| |
1007H | 1st group of Heating/Cooling | 1~990, unit is 0.1 second. When the output setting = realy, the minimum control | |
| control cycle | cycle is 5 second | |
1008H | 2nd group of Heating/Cooling | 1~990, unit is 0.1 second. When the output setting = realy, the minimum control | |
| control cycle | cycle is 5 second 1~990 | |
1009H | PB Proportional band | 0.1 ~ 999.9 | |
100AH | Ti Integral time | 0~9,999 | |
100BH | Td Derivative time | 0~9,999 | |
|
|
| |
100CH | Integration default | 0 ~ 100%, unit is 0.1% | |
|
|
| |
100DH | Proportional control offset error | 0 ~ 100%, unit is 0.1% | |
| value, when Ti=0 | ||
|
| ||
100EH | The setting of COEF when Dual | 0.01 ~99.99, unit is 0.01 | |
| Loop output control are used |
| |
100FH | The setting of Dead Band when |
| |
| Dual Loop output control are |
| |
| used |
| |
1010H | Hysteresis setting value of the | 0~9,999 | |
| 1st output group |
| |
1011H | Hysteresis setting value of the | 0~9,999 | |
| 2nd output group |
| |
1012H | Output value read and write of | Unit is 0.1%, write operation is valid under manual tuning mode only. | |
| Output 1 | ||
|
| ||
1013H | Output value read and write of | Unit is 0.1%, write operation is valid under manual tuning mode only. | |
| Output 2 | ||
|
| ||
1016H | Temperature regulation value | ||
|
|
| |
1017H | Analog decimal setting | 0 ~ 3 | |
101CH | PID parameter selection | 0~5/AUTO | |
101DH | SV value corresponded to PID | Only valid within available range, unit: 0.1 scale | |
| value | ||
|
| ||
1020H | Alarm 1 type | Please refer to the contents of the “Alarm Outputs” for detail | |
|
|
| |
1021H | Alarm 2 type | Please refer to the contents of the “Alarm Outputs” for detail | |
|
|
| |
1022H | Alarm 3 type | Please refer to the contents of the “Alarm Outputs” for detail | |
1024H | Please refer to the contents of the “Alarm Outputs” for detail | ||
|
|
| |
1025H | Please refer to the contents of the “Alarm Outputs” for detail | ||
|
|
| |
1026H | Please refer to the contents of the “Alarm Outputs” for detail | ||
1027H | Please refer to the contents of the “Alarm Outputs” for detail | ||
1028H | Please refer to the contents of the “Alarm Outputs” for detail | ||
|
|
| |
1029H | Please refer to the contents of the “Alarm Outputs” for detail | ||
|
|
| |
102AH | Read LED Status | b0: ALM3, b1: ALM2, b2: ℉, b3: ℃, b4: ALM1, b5: OUT2, b6:OUT1, b7: AT | |
102BH | Read Pushbutton Status | b1: F2, b2: Up, b3: Loop, b5: F1, b6: Down, b7: Set, 0: press down key | |
102CH | Setting lock status |
| |
|
|
| |
102FH | Software version | V1.00 indicates 0x100 | |
|
|
| |
1030H | Start pattern number | 0 ~ 15 | |
| Pattern 0~15 temperature set | ||
1200H~13FFH | point setting (Even number) | ||
Pattern 0~15 execution time | Time: 0 ~ 900(1 minute per scale) | ||
| |||
| setting (Odd number) |
| |
1400H~140FH | Actual number of step setting | 0 ~ 15 = N, indicate that this pattern is executed from step 0 to step N | |
inside the corresponding pattern | |||
|
| ||
| Cycle number for repeating the |
| |
1410H~141FH | execution of the correspond | 0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times | |
| pattern |
| |
1420H~142FH | Link pattern number setting of | 0 ~ 15, 16 indicates the program end and keep in present step. 17 indicates the | |
program end and execution end. 0~15 indicates the next execution pattern | |||
the correspond pattern | |||
| number after executing the current pattern | ||
|
| ||
|
|
| |
|
|
| |
Address | Content | Definition | |
1100H | Adjust Temperature Gain |
| |
|
|
| |
1101H | Temperature Filter Range | Range of temperature filter: 10~1000, unit: 0.01 ℃, default: 100(1.0℃) | |
1102H | Temperature Filter Factor | Setting range: 0~50, default: 8 |