1006H

Heating/Cooling control selection

Refer to Ouputput Mode Selection

 

 

 

1007H

1st group of Heating/Cooling

1~990, unit is 0.1 second. When the output setting = realy, the minimum control

 

control cycle

cycle is 5 second

1008H

2nd group of Heating/Cooling

1~990, unit is 0.1 second. When the output setting = realy, the minimum control

 

control cycle

cycle is 5 second 1~990

1009H

PB Proportional band

0.1 ~ 999.9

100AH

Ti Integral time

0~9,999

100BH

Td Derivative time

0~9,999

 

 

 

100CH

Integration default

0 ~ 100%, unit is 0.1%

 

 

 

100DH

Proportional control offset error

0 ~ 100%, unit is 0.1%

 

value, when Ti=0

 

 

100EH

The setting of COEF when Dual

0.01 ~99.99, unit is 0.01

 

Loop output control are used

 

100FH

The setting of Dead Band when

-999 ~ 9,999

 

Dual Loop output control are

 

 

used

 

1010H

Hysteresis setting value of the

0~9,999

 

1st output group

 

1011H

Hysteresis setting value of the

0~9,999

 

2nd output group

 

1012H

Output value read and write of

Unit is 0.1%, write operation is valid under manual tuning mode only.

 

Output 1

 

 

1013H

Output value read and write of

Unit is 0.1%, write operation is valid under manual tuning mode only.

 

Output 2

 

 

1016H

Temperature regulation value

-99.9 ~ +99.9. Unit is 0.1

 

 

 

1017H

Analog decimal setting

0 ~ 3

101CH

PID parameter selection

0~5/AUTO

101DH

SV value corresponded to PID

Only valid within available range, unit: 0.1 scale

 

value

 

 

1020H

Alarm 1 type

Please refer to the contents of the “Alarm Outputs” for detail

 

 

 

1021H

Alarm 2 type

Please refer to the contents of the “Alarm Outputs” for detail

 

 

 

1022H

Alarm 3 type

Please refer to the contents of the “Alarm Outputs” for detail

1024H

Upper-limit alarm 1

Please refer to the contents of the “Alarm Outputs” for detail

 

 

 

1025H

Lower-limit alarm 1

Please refer to the contents of the “Alarm Outputs” for detail

 

 

 

1026H

Upper-limit alarm 2

Please refer to the contents of the “Alarm Outputs” for detail

1027H

Lower-limit alarm 2

Please refer to the contents of the “Alarm Outputs” for detail

1028H

Upper-limit alarm 3

Please refer to the contents of the “Alarm Outputs” for detail

 

 

 

1029H

Lower-limit alarm 3

Please refer to the contents of the “Alarm Outputs” for detail

 

 

 

102AH

Read LED Status

b0: ALM3, b1: ALM2, b2: , b3: , b4: ALM1, b5: OUT2, b6:OUT1, b7: AT

102BH

Read Pushbutton Status

b1: F2, b2: Up, b3: Loop, b5: F1, b6: Down, b7: Set, 0: press down key

102CH

Setting lock status

 

 

 

 

102FH

Software version

V1.00 indicates 0x100

 

 

 

1030H

Start pattern number

0 ~ 15

 

Pattern 0~15 temperature set

-999 ~ 9999

1200H~13FFH

point setting (Even number)

Pattern 0~15 execution time

Time: 0 ~ 9001 minute per scale

 

 

setting (Odd number)

 

1400H~140FH

Actual number of step setting

0 ~ 15 = N, indicate that this pattern is executed from step 0 to step N

inside the corresponding pattern

 

 

 

Cycle number for repeating the

 

1410H~141FH

execution of the correspond

0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times

 

pattern

 

1420H~142FH

Link pattern number setting of

0 ~ 15, 16 indicates the program end and keep in present step. 17 indicates the

program end and execution end. 0~15 indicates the next execution pattern

the correspond pattern

 

number after executing the current pattern

 

 

 

 

 

 

 

 

Address

Content

Definition

1100H

Adjust Temperature Gain

 

 

 

 

1101H

Temperature Filter Range

Range of temperature filter: 10~1000, unit: 0.01 , default: 100(1.0)

1102H

Temperature Filter Factor

Setting range: 0~50, default: 8

18

Page 18
Image 18
Delta DT3 instruction sheet 999 ~ 9,999