Venting and Combustion Air Installation
NOTICE
The maximum equivalent length is the total length of the venting and the com- bustion air inlet combined. This includes termination fittings.
NOTICE
For Delta PERFORMANCE PLUS applications that may exceed the 100 feet maximum allowable equivalent length for the venting system, contact Triangle Tube Engineering Department for addi- tional information on how the appliance can be adjusted to the application.
-For each elbow included in the system, the maximum allowable linear length must be reduced as follows:
•Each 90º elbow within the system is the equivalent of 10 linear feet.
•Each 45º elbow within the system is the equivalent of 5 linear feet.
It is recommended that the installer uses the same number of elbows and length of piping on the venting system and the combustion air inlet.
Table 2- Allowable Equivalent Length (Combined Vent and Combustion Air)
Maximum | Total Elbows within the Venting / Combustion Air System | |||||
Allowable for |
|
|
|
|
|
|
Linear Length Combined | 2 | 3 | 4 | 5 | 6 | 7 |
PERFORMANCE PLUS | 180 | 170 | 160 | 150 | 140 | 130 |
| Fig. 19: Standard Vertical Venting Installation |
| Fig. 20: Vertical - Direct Vent Combination |
|
|
|
|
|
|
33