Verify Correct Pressure Switch
1.Remove the burner hood and verify the burner pressure switch setting.
2.Check and compare the color of the out- line on the pressure switch label to Table 3 page 49.
NOTICE
The PERFORMANCE PLUS is equipped with an air pressure switch, which provides a safe means of shutting down the unit due to a blockage of the combustion air inlet. The switch is “nor- mally closed” and measures the change in the negative pressure (vacuum) creat- ed by the burner blower.
Verify Correct Air Shutter Setting
-Check and verify the air shutter setting as listed in Table 4.
-The air shutter is located inside the com- bustion air inlet adapter located in the top /left jacket panel area. See Fig. 37.
Table 4 : Air Shutter Settings
Model | Natural Gas | Propane |
|
|
|
PG | 2.5 | 2.5 |
PG | 2.5 | 2.5 |
PG | 1 | 2.0 |
PG | N/R | 0 |
PG | N/R | 0 |
NR- Air shutter not required.
Check Thermostat Circuit
-Unplug the Room Thermostat
-Connect a voltmeter across the end ter- minals of the male half of the Room Thermostat
-Close each thermostat, zone valve and relay in the external circuit one zone at a time and check the voltage reading across the plug.
-There should NEVER be voltage mea- sured at the plug.
-If voltage is measured at the plug under any condition, check and correct the external wiring.
NOTICE
In systems using
Fig. 37: Air Shutter Adjustment