3.Fill the outer tank to correct system pressure. Correct pressure will vary with each application.
NOTICE
Typical residential system fill pressure is 12 psi. System pressure will increase when system temperature increases. Operating pressure of the system should never exceed 25 psi.
4.Allow air to escape from the outer tank by opening the automatic air vent provided with the PERFORMANCE PLUS.
5.Purge air in each zone of the primary sys- tem through the purge valve. Open air vents to allow air to be purged in the zones.
6.Once the system is completely filled and purged of all air, check the system pressure and check for leaks.
Check Low Water Cut-Off Device
- The PERFORMANCE PLUS is pro- vided with a factory installed Low Water
-Remove the front jacket panel and check for continuity across the low water cut- off device wire terminals. The contacts should be closed when system pressure is greater than 10 psi.
Check For Gas Leaks
WARNING
Prior to
WARNING
DO NOT adjust or attempt to measure gas valve outlet pressure. The gas valve is
WARNING
Propane installations only - The propane supplier mixes an odorant with the propane to make its presence detectable. In some cases the odorant can fade and the gas may no longer have an odor.
Prior to
Table 3 : Pressure Switch Setting
PG PLUS | Natural Gas | Propane |
Model | (inch w.c.) | (inch w.c.) |
|
|
|
PG | 1.84 " w.c. (yellow) | 1.84" w.c. (yellow) |
PG | 2.7" w.c. (red) | 2.7" w.c. (red) |
PG | 2.7 " w.c. (red) | 2.7" w.c. (red) |
PG | 2.7 " w.c. (red) | 3.35" w.c. (blue) |
PG | 2.7 " w.c. (red) | 3.35" w.c. (blue) |
|
|
|
49