Desa CRL3124P/N, CRL2718P/N, CGD3018PT/NT, CGD3924PT/NT Continued, Minimum Fireplace Clearance

Models: CGD3924PT/NT CGD3018PT/NT CRL3124P/N CRL2718P/N

1 44
Download 44 pages 38.64 Kb
Page 9
Image 9
MINIMUM FIREPLACE CLEARANCE

INSTALLATION

Continued

INSTALLATION AND CLEARANCES (Vent-Free Operation Only)

Manual background WARNING: Maintain the minimum clearances. If you can, provide greater clearances from floor, ceiling, and adjoining wall.

MINIMUM FIREPLACE CLEARANCE

TO COMBUSTIBLE MATERIALS

Log Size

 

Side Wall

 

Ceiling

 

 

 

 

 

 

 

 

18", 24", 30"

 

16"

 

 

42"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOG SIZING REQUIREMENTS

 

 

 

Minimum Firebox

Log

 

 

 

 

Front

 

Rear *

Size

 

Height

 

Depth

Width

 

Width

18"

 

17"

 

14"

24"

 

 

20"

24"

 

17"

 

14"

28"

 

 

21"

30"

 

17"

 

14"

34"

 

 

24"

* Measured at 14" depth.

Carefully follow the instructions below. This will ensure safe installation into a masonry, UL127- listed manufactured fireplace, or certified vent-free firebox.

Minimum Clearances For Side

Combustible Material, Side Wall, and

Ceiling

A.Clearances from the side of the fireplace cabi- net to any combustible material and wall should follow diagram in Figure 5.

Example: The face of a mantel, bookshelf, etc. is made of combustible material and pro- trudes 3 1/2" from the wall. This combustible material must be 4" from the side of the fire- place opening (see Figure 5).

Note: When installing your gas logs into a manufactured firebox, follow firebox manufacturer’s instructions for minimum clearances to combustible materials.

B.Clearances from the top of the fireplace opening to the ceiling should not be less than 42 inches.

Example

*

*Minimum 16 inches from Side Wall

Figure 5 - Minimum Clearance for

Combustible to Wall

NOTICE: Manual control heaters may be used as a vented prod- uct. If so, you must always run heater with chimney flue damper open. If running heater with damper open, noncombustible material above fireplace open- ing is not needed. Go to Install- ingDamperClampAccessoryfor Vented Operation, page 11.

Minimum Noncombustible Material Clearances

If Not Using Mantel

Note: If using a mantel, proceed to If Using Mantel, page 10. If not using a mantel, follow the informa- tion below.

You must have noncombustible material(s) above the fireplace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have non- combustible material behind it. Noncombustible material must extend at least 8" up (for all models). If noncombustible material is less than 12", you must install the fireplace hood accessory (24" and 30" models only). See Figure 6, page 10 for mini- mum clearances.

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chim- ney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 11.