Installation

Model SCS-RACK System Enclosure

Description

The SCS-RACK houses the receiver processor, power supply, line cards, and associated cables. The enclosure measures 8.75” high, 19” wide, and 12” deep.

Modem Rack

The SCS-RACK top portion holds the modem rack, which connects the SCS-110 Modem Power Supply Card and up to five line cards. The SCS-130 Transformer Card for connecting the 120 VAC mounts on the rear of the modem rack.

Multibus Rack

The bottom portion of the SCS-RACK holds the Multibus Rack, which holds the SCS-150 Receiver Processor Board and the SCS-120 Multibus Power Supply Card.

32-Character LCD Membrane Keypad

Mounted on the front faceplate of the SCS-RACK is a 32-character LCD Membrane Keypad. The LCD and keypad come pre-mounted and pre-wired with the power cable and ribbon cable.

Installing the SCS-RACK

Connect the SCS-RACK to earth ground before making any module connections. Use a minimum 14 gauge wire for grounding. A crimp type spade connector is provided for connecting the ground wire to the ground lug on the modem rack.

Rack Mounting

The SCS-1R must be mounted in a standard 19” rack for listed Fire Signaling applications. Simply slide the entire unit into the 19” rack and secure with screws. Refer to the drawing below for rack-mounting hole locations.

SCS-100 Digital Dialer

SCS-101 Network

Line Cards

Line Card

Rack-Mounting holes

SCS-150 Receiver

Processor Card

Digital Monitoring Products

SCS-1R Installation Guide

6