Intelligent Technologies (IT.) QSNAP
Pub. No. MN05001001E 11
February 2002
Input/Output Data
The QSNAP offers a standard data list (shown below) for default operation. The list is
congurable with data contained within Table 21 in Appendix A: QSNAP Parameters, using
the CH Studio application.
Input Data
Use Tables 10 and 11 when setting up the QSNAP input data.
Table 10: Input Assembly Data Definitions
Data Description
Faulted/Trip The motor controller is faulted or tripped
Warning The motor controller has a warning of an impending trip
Running 1 The rst motor controller is running
Running 2 The second motor controller is running
Permissive The motor controller run/stop permissive
Resetting Motor controller is in the process of resetting a fault
Thermal Capacity % thermal capacity of the motor from 0 to 100%
RMS Average
Current
Average RMS current of the motor (0.000A)
Fault Codes and
Warning Codes
Valid fault and warning codes are:
0 No Fault
1 General Fault
2 Firmware Fault
3 Interdevice Communication Fault
4 Control Voltage Low Fault
5 Control Device Overtemperature Fault
6 Motor Phase Loss Fault
7 Motor Phase Imbalance Fault
8 Motor Ground Fault
9 Motor Underload Fault
10 Motor Overcurrent Fault
13 Motor Bypass Failure Fault
14 Motor Thermal Pile Fault
15 Control Device Test Fault
40000 Current Threshold Warning
40001 Underload Warning
40002 Control Device Overtemperature Warning
40003 Overload Warning