| is dependent on system sizing, thermostat location, etc. Note: The thermostat display only |
13.Why does the system run |
| displays whole numbers. Internally the thermostat calculates decimals. |
with the setpoint and room |
| In heating as the room temperature increases the system will continue to run until the |
temperature the same? |
| |
| thermostat reaches the high side of the temperature setpoint. | |
|
| |
|
|
|
14. How do I reset my |
| There are 3 possibilities to consider, excluding tampering. |
thermostat? |
| 1. Loss of power from the system, 24VAC should be constant to maintain a display. |
|
| |
|
| 2. Static electricity or a voltage spike from the heating equipment might be resetting the |
|
| thermostat. Static electricity can be eliminated by touching something before touching the |
|
| thermostat to dissipate the static charge. A voltage spike from the equipment can be |
|
| eliminated using an isolation relay as described in the link below. |
|
| |
|
| You can also check the wire routing to verify the thermostat or remote wires are not running |
|
| parallel to high voltage lines with high inductive loads which could (in extreme cases) |
|
| create a voltage spike at the thermostat. |
|
| 3. Thermostat not functioning properly. A simple test would be to bench test one of the units |
|
| for a couple of days to see if it resets or move it to another system where a reset has never |
|
| occurred. |
|
|
|