TROUBLESHOOTING

TROUBLESHOOTING

RESETTING THERMOSTAT

The thermostat can be reset back to factory default programs and configuration options. Removing power from the thermostat will not reset it to the default settings. Before resetting the thermostat you may want to make note of the previously selected configura- tion options and programming.

To reset the thermostat, press and release PROGRAM RUN , then press the FAN , TIME BACK and RESETTING THERMOSTAT buttons at the same time. This will reset the thermostat to factory default programs and configuration. The display will momentarily go blank, and then all segments on the display will momentarily be shown. The thermostat will then go into the AUTO HOLD mode and will maintain a factory preset temperatures of 62°F in Heat or 85°F in Cool. To clear the HOLD TEMPERA- TURE overide press the PROGRAM RUN button.

SYMPTOM

 

POSSIBLE CAUSE

CORRECTIVE ACTION

 

No Heat/No Cool/No Fan

 

1. Blown fuse or tripped circuit

Replace fuse or reset breaker.

(common problems)

 

breaker.

 

 

 

2. Furnace power switch to OFF.

Turn switch to ON.

 

 

3. Furnace blower compartment

Replace door panel in proper position to engage

 

 

door or panel loose or not properly

safety interlock or door switch.

 

 

installed.

 

 

 

 

 

 