Image 11
Figure 6. Quick Connect Housing Pin-Out

Quick Installation Guide

00825-0100-4801, Rev HA February 2008

Rosemount 3051S

STEP 4 CONTINUED...

2.Place coupling nut over quick connect and wrench tighten to a maximum of 300 in-lb. (34 N-m).

3.Tighten the set screw using a 3/32-in hex wrench.

4.Install Cordset/ Field Wireable Connectors onto the Quick Connect. Do not over tighten.

Figure 6. Quick Connect Housing Pin-Out

For other wiring

 

details, refer to pin-out

“+”

drawing and the

“–”

cordset

No Connection

manufacturer’s

 

installation

Ground

 

instructions.

 

Conduit Electrical Connector Wiring (Option GE or GM)

For 3051S transmitters with conduit electrical connectors GE or GM, refer to the cordset manufacturer’s installation instructions for wiring details. For FM Intrinsically Safe, non-incendive or FM FISCO Intrinsically Safe hazardous locations, install in accordance with Rosemount drawing 03151-1009 to maintain outdoor rating (NEMA 4X and IP66.) See Appendix B of the 3051S reference manual.

11

Page 11