Installation

No special installation is required in addition to the standard installation practices outlined in this document. Always ensure a proper seal by installing the electronics housing covers so that metal contacts metal.

The loop should be designed so the terminal voltage does not drop below 10.5 Vdc when the transmitter output is 23.0 mA.

If hardware security switches are installed, the security switch should be in the “ON” position during normal operation. See Figure 2 on page 6. If hardware security switches are not installed, security should be “ON” in the software to prevent accidental or deliberate change of configuration data during normal operation.

Configuration

Use any HART-compliant master to communicate with and verify configuration of the 3051S Safety-Certified Pressure Transmitter (see Table 1 on page 13 and 14 to verify configuration).

User-selected damping will affect the transmitters ability to respond to changes in the applied process. The damping value + response time should not exceed the loop requirements.