Emerson manual Rosemount 3051S, Quick Installation Guide

Models: 3051S

1 36
Download 36 pages 50 Kb
Page 27
Image 27
Manual background

Quick Installation Guide

00825-0100-4801, Rev HA February 2008

Rosemount 3051S

Special Conditions for Safe Use (x)

The apparatus is not capable of withstanding the 500V insulation test required by Clause 9.1 of EN 50021: 1999. This must be taken into account when installing the apparatus.

ND ATEX Dust

Certificate No.: BAS01ATEX1374X Manual background II 1 D

T105°C (-20 °C ≤ Tamb ≤ 85 °C) Vmax = 42.4 volts max

A = 24 mA IP66

Manual background 1180

Special Conditions for safe use (x):

1.The user must ensure that the maximum rated voltage and current (42.4 volts, 22 milliampere, DC) are not exceeded. All connections to other apparatus or associated apparatus shall have control over this voltage and current equivalent to a category “ib” circuit according to EN 50020.

2.Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.

3.Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.

4.Cable entries and blanking plugs must be suitable for the ambient range of the apparatus and capable of withstanding a 7J impact test.

5.The 3051S must be securely screwed in place to maintain the ingress protection of the enclosure. (The 3051S SuperModule must be properly assembled to the 3051S housing to maintain ingress protection.)

27

Page 27
Image 27
Emerson manual Rosemount 3051S, Quick Installation Guide