Quick Installation Guide
Rosemount 3051S
STEP 2: CONSIDER HOUSING ROTATION
To improve field access to wiring or to better view the optional LCD display:
1.Loosen the housing rotation set screw.
2.First rotate the housing clockwise to the desired location. If the desired location cannot be achieved due to thread limit, rotate the housing counter clockwise to the desired location (up to 360° from thread limit).
3.Retighten the housing rotation set screw.
Figure 1. Transmitter Housing Set Screw
PlantWeb | Junction Box |
|
|
Housing Rotation Set
Screw
STEP 3: SET SWITCHES AND JUMPERS
If alarm and security adjustment option is not installed, the transmitter will operate normally with the default alarm condition alarm high and the security off.
Figure 2. Transmitter Switch and Jumper Configuration
PlantWeb
Meter/
Adjustment
Module
SecurityAlarm
Slide the security and alarm switches into the preferred position by using a small screwdriver.
(A LCD display or an adjustment module must be in place to activate the switches.)
Junction Box
Security Alarm
Pull the jumpers out and rotate 90° into desired position to set the security and alarm.