Emerson manual Rosemount 3051S, Quick Installation Guide, Switches installed

Models: 3051S

1 36
Download 36 pages 50 Kb
Page 20
Image 20
Switches installed

Quick Installation Guide

Rosemount 3051S

00825-0100-4801, Rev HA February 2008

Setting the alarm values and direction is dependent on whether or not the hardware switch option is installed. You can use a HART master or communicator to set the Alarm and Saturation values.

Switches installed

1.If using a communicator, use the following fast key sequence to set the Alarm and Saturation values.

Alarm Levels - Fast Key; 1, 4, 2, 7, 7 Saturation Levels - Fast Key; 1, 4, 2, 7, 8

2.Manually set the direction for the Alarm to HI or LO using the ALARM switch as shown in Figure 2 on page 6.

Switches not installed

If using a communicator, use the following fast key sequence to set the Alarm and Saturation values and the Alarm Direction:

Alarm Levels - Fast Key; 1, 4, 2, 7, 7 Saturation Levels - Fast Key; 1, 4, 2, 7, 8 Alarm Direction Fast Key; 1, 4, 2, 7, 6