Rosemount 3051S
Setting the alarm values and direction is dependent on whether or not the hardware switch option is installed. You can use a HART master or communicator to set the Alarm and Saturation values.
Switches installed
1.If using a communicator, use the following fast key sequence to set the Alarm and Saturation values.
Alarm Levels - Fast Key; 1, 4, 2, 7, 7 Saturation Levels - Fast Key; 1, 4, 2, 7, 8
2.Manually set the direction for the Alarm to HI or LO using the ALARM switch as shown in Figure 2 on page 6.
Switches not installed
If using a communicator, use the following fast key sequence to set the Alarm and Saturation values and the Alarm Direction:
Alarm Levels - Fast Key; 1, 4, 2, 7, 7 Saturation Levels - Fast Key; 1, 4, 2, 7, 8 Alarm Direction Fast Key; 1, 4, 2, 7, 6