Power Supply

Quick Installation Guide

Rosemount 3051S

00825-0100-4801, Rev HA February 2008

STEP 4 CONTINUED...

Power Supply

The dc power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, and related pieces. Note that the resistance of intrinsic safety barriers, if used, must be included.

Figure 7. Load Limitation

Standard Transmitter

Maximum Loop Resistance =

43.5 * (Power Supply Voltage – 10.5)

(Ohms)

1387

 

 

 

 

 

 

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Load

500

 

 

 

 

Operating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Region

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.5

20

30

Voltage (V dc)

42.4

 

HART Diagnostics Transmitter

(option code DA1)

Maximum Loop Resistance =

43.5 * (Power Supply Voltage – 12.0)

(Ohms)

1322

 

 

 

 

 

 

 

1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Load

500

 

 

 

 

 

Operating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Region

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12.0

20

30

Voltage (V dc)

42.4

 

The HART communicator requires a minimum loop

resistance of 250Ω for communication.