Quick Installation Guide
Rosemount 3051S
STEP 4 CONTINUED...
NOTE
Wire colors provided on page 9 are per Belden 3084A DeviceNet cable. Wire color may vary depending on cable selected.
Belden 3084A DeviceNet cable includes a ground shield. This shield must be connected to earth ground at either the SuperModule or the Remote Display, but not both.
Quick Connect Wiring
As standard, the 3051S Quick Connect arrives properly assembled to the SuperModule and is ready for installation. Cordsets and Field Wireable Connectors (in shaded area) are sold separately.
Figure 5. Rosemount 3051S Quick Connect Exploded View
Straight Field | Right Angle Field Wireable | |||||
Connector(2)(3) | ||||||
Wireable |
|
|
|
|
| |
Connector(1)(3) |
|
|
|
| Cordset(4) | |
|
|
|
|
|
| |
|
|
|
|
|
| |
|
|
|
|
| Coupling Nut | |
|
|
|
|
|
Quick Connect Housing
Quick Connect Coupling Nut
(1)Order part number 03151-9063-0001.
(2)Order part number
(3)Field wiring supplied by customer.
(4)Supplied by cordset vendor.
IMPORTANT
If Quick Connect is ordered as a 300S spare housing or is removed from the SuperModule, follow the instructions below for proper assembly prior to field wiring.
1.Place the Quick Connect onto the SuperModule. To ensure proper pin alignment, remove coupling nut prior to installing quick connect onto SuperModule.
10