Quick Installation Guide
Rosemount 3051S
STEP 5: VERIFY CONFIGURATION
Use any
A check (√) indicates the basic configuration parameters. At a minimum, these parameters should be verified as part of the configuration and startup procedure.
Table 1. HART Fast Key Sequence |
| |
|
|
|
| Function | Fast Key Sequence |
| Alarm Level Configuration | 1, 4, 2, 7, 7 |
|
|
|
| Alarm and Saturation Levels | 1, 4, 2, 7 |
| Analog Output Alarm Direction | 1, 4, 2, 7, 6 |
|
|
|
| Analog Output Trim | 1, 2, 3, 2 |
| Burst Mode On/Off | 1, 4, 3, 3, 3 |
|
|
|
| Burst Options | 1, 4, 3, 3, 4 |
√ Damping | 1, 3, 6 | |
|
|
|
| Date | 1, 3, 4, 1 |
| Descriptor | 1, 3, 4, 2 |
|
|
|
| Digital To Analog Trim | 1, 2, 3, 2, 1 |
| Output) |
|
| Field Device Information | 1, 4, 4, 1 |
|
|
|
| LCD Display Configuration | 1, 3, 7 |
| Loop Test | 1, 2, 2 |
|
|
|
| Lower Sensor Trim | 1, 2, 3, 3, 2 |
| Message | 1, 3, 4, 3 |
| Number of Requested Preambles | 1, 4, 3, 3, 2 |
|
|
|
| Pressure Alert Configuration | 1, 4, 3, 5, 3 |
| Poll Address | 1, 4, 3, 3, 1 |
|
|
|
| Poll a Multidropped Transmitter | Left Arrow, 3, 1, 1 |
| Remapping | 1, 4, 3, 6 |
|
|
|
| Rerange- Keypad Input | 1, 2, 3, 1, 1 |
|
|
|
Continued on Next Page
13