Emerson manual Hazardous Locations Certifications, Rosemount 3051S, Quick Installation Guide

Models: 3051S

1 36
Download 36 pages 50 Kb
Page 25
Image 25

Quick Installation Guide

00825-0100-4801, Rev HA

February 2008

Rosemount 3051S

 

 

 

Hazardous Locations Certifications

North American Certifications

FM Approvals

E5 Explosion proof for Class I, Division 1, Groups B, C, and D; dust-ignition proof for Class II and Class III, Division 1, Groups E, F, and G; hazardous locations; enclosure Type 4X, conduit seal not required when installed according to Rosemount drawing 03151-1003.

I5 Intrinsically Safe for use in Class I, Division 1, Groups A, B, C, and D; Class II, Division 1, Groups E, F, and G; Class III, Division 1; Class I, Zone 0 AEx ia IIC when connected in accordance with Rosemount drawing 03151-1006; Non-incendive for Class I, Division 2, Groups A, B, C, and D, Enclosure Type 4X

For entity parameters see control drawing 03151-1006.

Canadian Standards Association (CSA)

E6 Explosion-Proof for Class I, Division 1, Groups B, C, and D; Dust-Ignition-Proof for Class II and Class III, Division 1, Groups E, F, and G; suitable for Class I, Division 2, Groups A, B, C, and D, when installed per Rosemount drawing 03151-1013, CSA Enclosure Type 4X; conduit seal not required.

I6 Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D when connected in accordance with Rosemount drawings 03151-1016;

For entity parameters see control drawing 03151-1016.

25

Page 25
Image 25
Emerson manual Hazardous Locations Certifications, Rosemount 3051S, Quick Installation Guide