STEP 5: CONFIGURE THE TRANSMITTER (FIELDBUS)

Quick Installation Guide

Rosemount 3095 MultiVariable

00825-0100-4716, Rev DA October 2009

STEP 5: CONFIGURE THE TRANSMITTER (FIELDBUS)

Each FOUNDATION fieldbus host or configuration tool has a different way of displaying and performing configurations. Some use Device Descriptions (DD) or DD methods for configuration and to display data consistently across platforms. There is no requirement that a host or configuration tool support these features.

Use the following block examples to do basic configuration to the transmitter. For more advanced configurations including configuring the 3095 Mass Flow transducer block, see the 3095 Manual (00809-0100-4716).

NOTE

DeltaV users should use DeltaV Explorer for the Resource and Transducer blocks and Control Studio for the Function Blocks.

Send the Configuration to the Transmitter

Use the following steps to create and send the mass flow configuration to the Mass Flow Transducer Block.

NOTE

All previous Mass Flow transducer block information will be overwritten when the configuration is sent.

1.Open the 3095 Engineering Assistant for FOUNDATION fieldbus.

2.Select scan to scan the FOUNDATION fieldbus segment and select the device requiring the new or updated mass flow configuration file.

3.Select the EA Wizard.

4.Step through the Flow Configuration Wizard to create a mass flow configuration file.

5.Save the new or updated mass flow configuration file. Files must be saved for future review or update. Files cannot be uploaded from the Mass Flow Transducer Block.

6.Select send to send the mass flow configuration file to the selected transmitter Mass Flow Transducer Block.

To configure the AI Block

AI Block configuration parameters

 

 

 

 

 

 

Parameters

Enter Data

 

 

 

 

Channel

1

= Pressure

 

 

 

 

 

2

= Static Pressure

 

 

 

 

 

3

= Process Temperature

 

 

 

 

4

= Device Temperature

 

 

 

 

5

= Mass Flow

 

 

 

 

L_Type

Direct, Indirect, or Square Root

 

 

 

XD_Scale

Scale and Engineering Units

 

 

 

(Note: Only select the units that are supported by the device.)

 

 

 

 

Pressure:

 

 

 

 

 

 

Pa

bar

inH20 @ 68°F

 

psi

inHg @ 0°C

 

kPa

mbar

mmH20 @ 68°F

g/cm2

mmHg @ 0°C

 

mPa

atm

ftH20 @ 68°F

 

kg/cm2

mmH20 @ 4°C

 

Temperature:

 

 

torr

inH20 @ 4°C

 

 

 

 

 

 

°C

°F

K

 

 

 

 

Mass Flow Rate:

 

 

 

 

 

lbm/sec

lbm/min

lbm/hr

lbm/day

kg/sec

 

 

kg/min

kg/hour

g/sec

g/min

g/hr

 

 

StdCuFt/sec

StdCuFt/min

 

 

 

 

StdCuFt/hr

 

StdCuFt/day

 

StdCuM/sec

 

 

StdCuM/min

StdCuM/hr

 

StdCuM/day

 

Out_Scale

Scale and Engineering Units

 

 

 

16

Page 16
Image 16