Conditions of Certification (X):

Quick Installation Guide

00825-0100-4716, Rev DA October 2009

Rosemount 3095 MultiVariable

Table 7. RTD Terminals Entity Parameters

Uo = 30Vdc

Io = 19 mAdc

Po = 140 mW

The capacitance and either the Inductance or the Inductance to Resistance Ratio (L/R) of the load connected to the 4-pin connector must not exceed the following values:

Group

Capacitance (￿F)

Inductance (mH)

or L/R Ratio

 

 

 

￿H/Ohm

IIC

0.066

96

247

IIB

0.56

365

633

IIA

1.82

696

633

NOTE

1.The external circuit contains no combined lumped inductance and capacitance greater than 1% of the above values.

Or 2. The inductance and capacitance are distributed as in a cable.

Or 3. The external circuit contains only lumped inductance or only lumped capacitance in combination with a cable.

In all other situations e.g. combined lumped inductance and capacitance, up to 50% of each of L and C values is allowed.

Conditions of Certification (X):

When fitted with the transient option, the apparatus is not capable of withstanding the 500V electrical strength test as defined in Clause 6.3.12 of IEC 60079-11. This must be taken into account during installation.

5IECEx Type n

Certificate Number: IECEx BAS06.0071X Ex nA nL IIC T4 (-45°C Ta 70°C)

Ex nA nL IIC T5 (-45°C Ta 40°C) Ui = 55V dc max

Conditions of Certification (X):

When fitted with the transient option, the apparatus is not capable of withstanding the 500V electrical strength test as defined in Clause 6.8.1 of IEC 60079-15. This must be taken into account during installation.

7IECEx Flameproof

Certificate Number: IECEx KEM 06.0018 Zone 0/1 Ex d IIC T6 (-20°C Ta 65°C) Zone 0/1 Ex d IIC T5 (-20°C Ta 80°C)

Vmax = 55 Vdc

Imax = 23 mAdc

8IECEx Dust

Certificate Number: IECEx KEM 06.0018 Ex tD A22 T90°C

IP66

INMETRO Certifications

EINMETRO Flameproof BR-Ex d IIC T6/T5

21

Page 21
Image 21