Canadian Standards Association (CSA)

Quick Installation Guide

00825-0100-4716, Rev DA October 2009

Rosemount 3095 MultiVariable

Canadian Standards Association (CSA)

CExplosion Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F, and G. CSA enclosure Type 4X suitable for indoor and outdoor hazardous locations. Provides nonincendive RTD connection for Class I, Division 2, Groups A, B, C, and D.Factory Sealed. Install in accordance with Rosemount Drawing 03095-1024. Approved for Class I, Division 2, Groups A, B, C, and D.

KIntrinsically Safe for Class I, Division 1, Groups A, B, C, and D. when installed in accordance with Rosemount drawing 03095-1021. Temperature Code T3C.

For input parameters and installation see control drawing 03095-1021.

European Certifications

FATEX Intrinsic Safety

Certificate Number: BAS98ATEX1359X European Certifications II 1 G

Ex ia IIC T5 (Tamb = –45 °C to 40 °C) Ex ia IIC T4 (Tamb = –45 °C to 70 °C) Special Conditions for Safe Use 1180

Table 3. Connection Parameters (Power/Signal Terminals)

Ui = 30V

Ii = 200 mA

Pi = 1.0 W

Ci = 0.012 µF

Li = 0

Table 4. Temperature Sensor Connection Parameters

Uo = 30V

Io = 19 mA

Po = 140 mW

Ci = 0.002 µF

Li = 0

Table 5. Connection Parameters for Temperature Sensor Terminals

Co = 0.066 ￿F

Gas Group IIC

Co = 0.560 ￿F

Gas Group IIB

Co = 1.82 ￿F

Gas Group IIA

Lo = 96 mH

Gas Group IIC

Lo = 365 mH

Gas Group IIB

Lo = 696 mH

Gas Group IIA

Lo/Ro = 247 ￿H/ohm

Gas Group IIC

Lo/Ro = 633 ￿H/ohm

Gas Group IIB

Lo/Ro= 633 ￿H/ohm

Gas Group IIA

Special Conditions for Safe Use