IECEx Certifications (HART)

Quick Installation Guide

Rosemount 3095 MultiVariable

00825-0100-4716, Rev DA October 2009

GATEX Type n

Certificate Number: BAS98ATEX3360X Manual background II 3 G

Ex nL IIC T5 (Tamb = –45 °C to 40 °C) Ex nL IIC T4 (Tamb = –45 °C to 70 °C) Ui = 55V

The apparatus is designed for connection to a remote temperature sensor such as a resistance temperature detection (RTD)

Special Conditions for Safe Use

The 3095, when fitted with the transient terminal block (order code B), are not capable of withstanding the 500 volts insulation test required by EN60079-15 Clause 6.8.1. This condition must be accounted for during installation.

HATEX Flameproof

Certificate Number: KEMA02ATEX2320X Manual background II 1/2 G Ex d IIC T5 (-50°C Tamb 80°C)

T6 (-50°C Tamb 65°C)

Manual background 1180

Special Conditions for Safe Use (x):

The device contains a thin wall diaphragm. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.

PATEX Dust

Certificate Number: KEMA02ATEX2321 Manual background II 1 D Ex tD A20 T 90°C(-40°C Tamb 80°C)

V = 55 Vdc MAX I = 23 mA MAX IP66

Manual background 1180

IECEx Certifications (HART)

4IECEx Intrinsic Safety

Certificate Number: IECEx BAS06.0070X Ex ia IIC T4 (-45°C Ta 70°C)

Ex ia IIC T5 (-45°C Ta 40°C)

Table 6. Input Parameters

HART I.S.

Ui = 30Vdc

Ii = 200 mAdc

Pi = 1.0 W

Ci = 12 nF

Li = 0

20

Page 20
Image 20