Emerson 00825-0100-4716 manual Rosemount 3095 MultiVariable, Quick Installation Guide

Models: 00825-0100-4716 3095

1 32
Download 32 pages 51.72 Kb
Page 26
Image 26
Manual background

Quick Installation Guide

Rosemount 3095 MultiVariable

00825-0100-4716, Rev DA October 2009

Table 9. Temperature Sensor Connection Parameters

Uo = 30V

Io = 19 mA

Po = 140 mW

Table 10. Connection Parameters for Temperature Sensor Terminals

Co = 0.066 ￿F

Gas Group IIC

Co = 0.560 ￿F

Gas Group IIB

Co = 1.82 ￿F

Gas Group IIA

Lo = 96 mH

Gas Group IIC

Lo = 365 mH

Gas Group IIB

Lo = 696 mH

Gas Group IIA

Lo/Ro = 247 ￿H/ohm

Gas Group IIC

Lo/Ro = 633 ￿H/ohm

Gas Group IIB

Lo/Ro= 633 ￿H/ohm

Gas Group IIA

Special conditions for safe use (x):

Versions of the apparatus fitted with the transient protected terminals are not capable of withstanding the 500 volts insulation test required by Clause 6.4.12 of EN 50020:2002. This must be taken into account when installing the apparatus.

GATEX Type N

Certificate Number: Baseefa05ATEX0023X

Manual background II 3 G

EEx nA nL IIC T5 (Tamb = –45 °C to 40 °C) EEx nA nL IIC T4 (Tamb = –45 °C to 70 °C) Ui = 55V

RTD Terminals - The apparatus is designed for connection to a remote temperature sensor such as a resistance temperature detection (RTD).

Special Conditions for Safe Use

Versions of the apparatus fitted with the transient protected terminals are not capable of withstanding the 500 volts insulation test required by Clause 8.1 of EN 60079-15:2003. This must be taken into account when installing the apparatus.

HATEX Flameproof

Certificate Number: KEMA02ATEX2320X

Manual background II 1/2 G

EEx d IIC T5 (-50°C Tamb 80°C) T6 (-50°C Tamb 65°C)

Vmax = 55 Vdc MAX Imax = 23 mA MAX IP66

Manual background 1180

Special conditions for safe use (x):

The device contains a thin wall diaphragm. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.

26

Page 26
Image 26
Emerson 00825-0100-4716 manual Rosemount 3095 MultiVariable, Quick Installation Guide, Special conditions for safe use