STEP 2 CONTINUED...

Quick Installation Guide

Rosemount 3095 MultiVariable

00825-0100-4716, Rev DA October 2009

STEP 2 CONTINUED...

3.Set the Failure Mode Alarm (HART devices), which is located on the front of the electronics board inside the electronics housing cover. The Alarm Jumper position determines if the output is driven high or low when a failure is detected. The transmitter operates normally if the jumpers are not installed and the Alarm default fail is HI.

Figure 2. Alarm Jumper Location

Security Jumper

Simulate Jumper

HART Electronics Board

FOUNDATION fieldbus Electronics Board

4.Set the Simulate Jumper (FOUNDATION fieldbus devices), which is located on the front of the electronics board inside the electronics housing cover. The jumper is used to simulate the measurement and is used as a lock-out feature for the AI function block. To enable the simulate feature, insert the jumper across ENABLE while the transmitter is powered. The default position for the Simulate Jumper is DISABLE. Enable the simulate feature after power is applied to the device. Simulate is automatically disabled regardless of jumper position if power is cycled.

5.Connect the transmitter to the process.

6.Install the RTD Cable Assembly (optional). All RTD 3095 Cable Assemblies use the 3095 RTD Cable Connector. Identify the cable type being installed and follow the steps below.

Installing an Armored Shielded RTD Cable (See Figure 3)

a.Fully engage the black cable connector to the 3095 RTD connector. b.Tighten the cable adapter until metal contacts metal.

c. Install the compression fitting.

d.Tighten the cap onto the compression fitting.

Figure 3. Armored Shielded RTD Cable

Compression Fitting

Black Cable Connector

Connect

Conductive Bushing

Cable Adapter

to RTD

RTD Cap Cap

3/4 to 1/2-14 NPT Adapter

Washer

Bushing

 

 

Compression Fitting

6

Page 6
Image 6