2 --- 1 1 Settings
Engine Exerciser Settings
The controller (CP) engine exerciser setti ngcan be di splayed and changed from
the keypad. Some settings may require a password (i fthe contr oller is set up for
one).
From any o f the Status displays, press Enter/Save Settings keytomove tothe
Settings level of menus.
Press the right arrow key to move to Setting Time Delays menu.
Press the right arrow key again to move to Settings Features menu.
Press the right arrow key again to move to Settings General menu.
Press the right arrow key again to move to Settings Engine Exercise r.
Now press Enter/Save Settings keytomovetothefirstEngine Exerciser menu.
Youcan press the right arrow key to see the other Engine Exerciser menus
(as shown below). An overviewexplanation of each setting is listed below.
8 Engine Exerciser Settings Menus
(last menu loops back to first)
Present Date/Time seepage21
This display allows the user to change the controlle r date and time.
US DST — US DaylightSaving Time. APR– OCT,MAR – NOV,or OFF.
MAR – NOV begins in 2007.
P(1—7) Engine Exercise r(s) seepage21
These displays (P1 through P7) allow the user to set the controller’sseven
independent engine exerciser routines . Each routine functions in the same
manner. Sixparameters need to be configured for each routine (P1, P2, P3,
P4, P5, P6, P7 — not all have to beused).
Enable — YES enables the routine; NO turns it off.
wLoad — YES transfers load to Emergency;NO = no transfer.
Start — when the routine will start the generator
– time (hour, minute)
– week (all, alternate, 1st, 2nd, 3rd, 4th, or 5th week)
–dayoftheweek(mon,tue,wed,thu,fri,sat,sun)
RunTime — duration (length of time) that the generator will run.
SETTINGS
VoltageDO P U
Frequency DO PU
PRESENT DATE/TIME
US DST:
Date:
Time:
P1 ENGINEEXER CISER
Enable: wLoad:
Start: h
Run Time: h min
SETTINGS
EngineExerciser
②③
④⑤
P7 ENGINEEXER CISER
Enable: wLoad:
Start: h
Run Time: h min
Set the seven
independent
engine exercise
routines,
if desired.