A --- 4Appendix

Voltage Jumper Blocks
Toavo idperma nently damaging the Group 5
controller,be certain that the voltage setting
matches the transfer switch system voltage.
Eight jumper blocks on the Group 5 controller are
arranged in one of two patterns for the power supply to
meet the requirements of the 16 different vol tage
inputs(shown in TableB on page A–2). These jumpers
are located on the front right side near the ribbon
cable. See Figures A–3 and A–4.
jumper blocks
(see Figure A–4)
Note: Also see page A–2 for
Nominal Source Voltage Selection
DIP switch actuator settings.

Figure A–3. Location of jumper blocks.

Nominal voltage Nominalvolt age
115 — 277 V 380— 600 V
(115, 120, 208, 220, 230, 240, 277) (380, 400, 415, 440, 460, 480, 550, 575, 600)
Position jumpers HORIZONTALLY Position jumpers VER TICALLY

Figure A–4. Power sup ply jumper arrangements.