2 --- 1 0Settings

Engine Exerciser Settings

Unless otherwise specified on the order, the controller engine exe rciser settings

are set at the factory to the default values. If a setting must be changed, follow the

procedure on the next page. Some settings ma y require a password (if the

controllerissetupforone).

Any indiscriminate change in these setting s may affect the normal
operation of the Automatic Transfer Switch. This cha nge could allow
the load circuits to remain connected to an inadequate source
Parameter Def ault Setting Adjustment Range Display Screen
(see next page)
month JAN
JAN, FEB, MAR,
APR, MAY,JUN, JUL,
AUG, SEP,OC T,
NOV,DEC
PRESENT DATE/TIME
Date
day 11to31 PRESENT DATE/TIME
Date
year * 100to 99 PRESENT DATE/TIME
Date
hour 10to23 PRESENT DATE/TIME
Time
minute 10to59 PRESENT DATE/TIME
Time
engine exerciser enable
(P1 to P7) no yes or no P1ENGINE EXERCISER
Enable
engine exerciser transfer load
(P1 to P7) no yes or no P1ENGINE EXERCISER
wLoad
engine exerciser start hour
(P1 to P7) 00to23 P1 ENGINE EXERCISER
Start h
engine exerciser start minute
(P1 to P7) 00to59 P1 ENGINE EXERCISER
Start min
engine exerciser run week
(P1 to P7) all
all, alternate,
first, second, third,
fourth, or fifth
engine exerciser run day
(P1 to P7) SUN SUN,MON, TUE ,
WED, THU, FRI,SAT
engine exerciser duration hours
(P1 to P7) 00to23 P1 ENGINE EXERCISER
Run TIme h
engine exerciser duration minutes
(P1 to P7) 00to59 P1 ENGINE EXERCISER
Run TIme min

* For the year 2000, enter 00.