Voltage & Frequency Settings

Unless otherwise specified on the order, the controller voltage and frequency

settings are set at the factory to the default values . I fa s ettingm ust be changed,

carefully follow the procedure on the next page. Some settings may require a

password (if the controller is set up for one).

Any indiscriminate change in these setting s may affect the normal
operation of the Automatic Transfer Switch. This cha nge could allow
the load circuits to remain connected to an inadequate source.
Description Settings Default Setting
%ofnominal
Adjustment Range
increments of 1%
Display Screen
(see next page)
Dropout 85 % 70 to 98 % NORMAL VOLTAGE
Dropout
Pickup 90 % 85 to 100 % NORMAL VOLTAGE
Pickup
Normal
S
o
u
r
c
e
Over Voltage Trip * off 102 to 115 % NORMAL VOLTAGE
OV Trip
S
ource
Voltage Unbalance Enable no yes or no NORMALVOLTAGEUNBAL
Enable
Unbalance Dropout 20 % 5to20% NORMALVOLTAGEUNBAL
Dropout
Unbalance Pickup 10 % 3to18% NORMALVOLTAGEUNBAL
Pickup
Dropout 75 % 70 to 98 % EMERG VOLTAGE
Dropout
Pickup 90 % 85 to 100 % EMERG VOLTAGE
Pickup
Emergency
S
o
u
r
c
e
Over Voltage Trip * off 102 to 115 % EMERG VOLTAGE
OV Trip
S
ource
Voltage Unbalance Enable no yes or no EMERG VOLTAGEUNBAL
Enable
Unbalance Dropout 20 % 5to20% EMERG VOLTAGE UNBAL
Dropout
Unbalance Pickup 10 % 3to18% EMERG VOLTAGE UNBAL
Pickup
l
Dropout 90 % 85 to 98 % NORMALFREQUENCY
Dropout
Normal
Source
F
r
e
q
u
e
n
c
y
Pickup 95 % 90 to 100 % NORMAL FRE QUENCY
Pickup
F
r
e
q
u
e
n
c
y
Over Frequency Trip* off 102 to 110 % NORMAL FREQUENCY
OF Trip
E
Dropout 90 % 85 to 98 % EMERG FREQUENCY
Dropout
Emergency
Source
F
r
e
q
u
e
n
c
y
Pickup 95 % 90 to 100 % EMERGFREQUENCY
Pickup
F
r
e
q
u
e
n
c
y
Over Frequency Trip* off 102 to 110 % EMERG FREQUENCY
OF Trip
* The Over Voltage and OverFrequency reset is fixed at 2% below the trip setting.