2 --- 4Settings

Time Delay Settings

Unless otherwise specified on the order, the Control ler time delay settings are set at the

factory to the default values. If a setting must be changed, follow the proce dure on the

next page. Some settings may require a password (if controller is set up for one) .

Any indiscriminatechange in these settings may affectthe normal operation of the Automatic Trans-
fer Switch. This change could allow the load circuits to remain connected to an inadequate source.
Feature Time D elay Def ault Setting Adjustment Range
1 sec. increments
Display Screen
(see next page)
1C override momentary
Normal source outages 1second 0to6sec
see CAUTION below TD NormFail
1F override momentary
Emergency source outages 00to60min59sec TDEmrgFail
2B transfer to Emergency 00to60min59sec TDN>E
2E unloaded running
(engine cooldown) 5 minutes 0to60min59sec TD EngCool
3
A
retransfer to Normal
(if Normal fails) 30 minutes 0to60min59sec TDE>N if
Normal Fail
3
A
retransfer to Normal
(if just a test) 30 seconds 0 to 9 hours
59 min 59 sec
TD E>N if
Tes t Mod e
31F Normal to Emergency
pre–transfer signal 00to5min59sec TD N>E Xfer Signal
PreXfer
31M Normal to Emergency
post–transfer signal 00to5min59sec TDN>E Xfer Signal
PostXfer
31F,31M bypass 31F & 31M
if Normal fails no yes or no TD N>E Xfer Signal
BypassIfNFail
31G Emergency to Normal
pre–transfer signal 00to5min59sec TD E>N Xfer Signal
PreXfer
31N Emergency to Normal
post–transfer signal 00to5min59sec TDE>N Xfer Signal
PostXfer
31G, 31N bypass31G & 31N
if Emergency fails no yes or no TD E>N Xfer Signal
BypassIfEFail
4
A
C
T
S
,
in sync 1.5 second 0to3.0seconds
0.1 sec increments
CTTS TD
SyncMonitorTD
4
A
C
T
S
,
7ACTS,
7ACTB
l
failure to synchronize 5 minutes 0to5min59sec CTTS TD
FailToSyncT D
only
extended parallel time 0.5 second 0.100 to 1.000 sec
0.01 sec increments
CTTS TD
XtdParallelTD
4ADTS,
7ADTS/B
onlydelay transition time 00to5min59sec DTTS TD
LoadDisconnDelay
These time delays appear only on the displayfor a 4ACTS, 7ACTS, or 7ACTB closed–transition transfer switch.
This time delay appears only on the display for a 4ADTS, 7ADTS, or 7ADTB delayed–transitiontransfer switch
Standard adjustment up to 6 seconds (totalpower outage). For additional time delay contact ASI. See CAUTION.
If output contacts required, contact ASI at 1–800–800–2726.
Do not set Feature 1C TD longer than 6 sec. unless an external 24 V dc
power supply is included. Contact ASI if longer than 6 sec. is required.