2 --- 8Settings

Y–YPrimaryFailureDetection(not shown) see page 2–1

This display shows status of a special control algorithm which is described in
Application Note 381339–276.
Enable Yes means the algorithm is activated to detect Normal primary single
phase failure in Y–Y systems.
Sense Delay — 1 second default time delay.
TD E>N YY— 1 hour defaulttime delay.
Note: Thisfunction s hould only be considered for use where the Norm al source
is provided through a Y–Y transformer. This function requires the Normal
source voltage unbalancemonitoring to be enabled.
General Settings
Unless otherwise specifiedon the order, the controller general settingsare set at
thefactory to the default val ues. I fa s etting must be changed, follow the procedure
on the next page. Some settings may require a password (if the controller is set
up for one).
Any indiscriminate change in these setting s may affect the normal
operation of the Automatic Transfer Switch. This cha nge could allow
the load circuits to remain connected to an inadequate source
Parameter Def ault Setting Adjustment Range Display Screen
(see next page)
language ENGLISH*
ENGLISH
FRENCH CDN
ENGLISH EU
ENGLISH EU S1–S2
ENGLISH S1–S2*
SPANISH
GERMAN
PORTUGUESE
Menu Language
ENGLISH
serial communications baud rate 19.2k
off, x9600, 9600,
19.2k, Mbus9600,
Mbus19.2k
SERIAL
COMMUNICATION
Baud Rate
serial communications address 10to63
SERIAL
COMMUNICATION
Address
event log enable no yes or no EVENTLOGGING
Enable
print enable no yes or n o EVENT LOGGING
Print Enable
clear log no yes or no EVENTLOGGING
Clear Log
door–mounted user controls locked
but not the Power Control Center
(this setting on 4000 Series only)
no yes or no Keypad Locked
password 1111 4characters
letters or numbers
Change
Password

*Note: If the language setting ENGLISH S1–S2 is selected the usual display words

Normal (N) and Emergency (E) are changed to Source 1 (S1) and Source 2 (S2).