2 --- 6Settings

Features Settings

Unless otherwisespecified on the order, the controller featuressettings are set at the

factory to the default values. Ifa se tting must be changed, follow the procedure onthe

next page. Some settings may require a password ( if the controller is set up for one).

Any indiscriminatechange in these settings may affectthe normal operation of the Automatic Trans-
fer Switch. This change could allow the load circuits to remain connected to an inadequate source.
Feature Default Setting Adjustment Range Display Screen
(see next page)
commit to transfer no yesor no Commit to Xfer A fter
TD Norm Fail
shed load direction from E from N or from E SHED LOAD
Direction
shed load in phase no yes or no SHED LOAD
InPhase
shed load in phase time delay 1.5 second 0to3.0seconds
0.1 sec increments
SHED LOAD
TD
shed load isolate load
on source failure yes yes or no SHED LOAD
IsoLoadOnSrcFail
shed load isolate loadon test 17 no yes or no SHEDLOAD
IsoLoadOnTest17
phase rotation monitor enable no yes or n o
PHASE ROTATION
MONITOR
Enable
phase rotation monitor referen ce ABC ABC or CBA
PHASE ROTATION
MONITOR
Reference
inphase monitor enable no yes or no
IN–PHASE
MONITOR
Enable
inphase monitor time delay 1.5 second 0to3.0seconds
0.1 sec increments
IN–PHASE
MONITOR
Time Delay
failure to sync auto bypass no yes or no CTTS BYPASS/SHEDLD
FailSync AutoB yps
bypass time delay 0second 0to59seconds
1 sec increments
CTTS BYPASS/SHEDLD
Bypass DT Delay
bypass in phase no yes or no CTTS BYPASS/SHEDLD
Bypass InPhase
Y–Y primary failure detection enable no yes or no Y–Y PRI FAIL DETECT
Enable
Y–Y primary failure sensing time delay 1.0 second 0to9.9seconds
0.1 sec increments
Y–Y PRI FAIL DETECT
Sense Delay
Y–Y primary failure retransfer time delay 1.0 hour 0to23hrs59min.
1 min. increments
Y–Y PRI FAIL DETECT
TD E>N Y–Y
These features appear only on the display fora 4ACTS, 7ACTS, or7ACTB closed–transition transfer switch.
These features appear only on t he display for a 4ACTS, 7ACTS or 7ACTB closed–tra nsition transfer switch
or a 4ADTS, 7ADTS, or 7ADTB delayed–transition transfer switch.
These features do not appear on the display unless boths ourceshave 3 phase sensing enabled.
These features appear only on a 4 ATS,7 ATS,or 7 ATB(op en–transition automatic transfer sw itch).