Installation
2.4Connect Power to the Liqui-tect Panel
The
! WARNING
Check that power is removed from wires prior to installation.
! CAUTION
The
This equipment is intended to be installed by a qualified and certified electrician who must review and approve customer supplied wiring and circuit breakers, verify correct input and grounded (earthed) connections to ensure compliance with technical standards and national and local electrical codes.
! WARNING
Be sure that the power wiring is disconnected from the
2.4.1Input Power Connections - Small Enclosure
To connect electrical power:
1.Run conduit and electrical wiring from building to the
2.Use copper wires only; proper wiring to use for 24VAC power is
Figure 5 Electrical connections to panel
External wiring through knockout
Ground wire (black)
Earth ground
R4
TB1
24V Power | TVS3 | FB2 |
|
terminal
24VAC wiring (red & white)
EGND1
Reset
SW3
24VAC input connector
3.Secure the incoming electrical service wires to the
10