System and Control Options
6.2Setup System - Overview
The Setup System screen displays six options that allow you to configure zones with cable, alarm outputs, the
•Setup ZN1 Zone 1
•Setup ZN2 Zone 2
•Setup Alarm Outputs
•Setup
•Setup Mapmode
•Setup System Info
6.3Setup System - Setup ZN1 Zone 1
The
If neither zone is configured as connected, the screen displays the message:
WARNING! NO ZONES ARE INSTALLED
Setup System Menu
>SETUP ZN1 ZONE 1 SETUP ZN2 ZONE 2
SETUP ALARM OUTPUTS ↑↓ =NEXT ↵ =SELECT
SETUP REALARM DELAY SETUP MAPMODE SETUP SYSTEM INFO
To configure the first zone:
Log In and Choose Setup System
• From the Main Menu, use the arrows ↑↓ to choose System and Control, then press Enter ↵ (see 6.1 - Login for help).
• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows ↑↓ to choose Setup System, then press Enter ↵ .
Select Zone 1 to Configure
Setup Zone 1 Menu
SETUP ZN1 ZONE 1
>CONNECTED: N
LABEL: ZONE 1
↑↓ =NEXT ↵ =SELECT
UNITS: FT
AUTO CALIBRATE WATER DETECT:150 UA CONTAMINATED:050 UA
• From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup ZN1 Zone 1 and press Enter ↵ .
• Use the steps following Table 8 to change the default settings for Zone 1.
Table 8 shows the features you may change for Zone 1, along with the default settings. By default, Zone 1 is not connected.
To activate Zone 1, you must specify it as connected. Other features that may be altered include the name of the zone, the measurement units, and the sensitivity for detection of water and of contamina- tion. You may also initiate automatic calibration, during which the
Table 8 | Default settings - Zone 1 |
| ||
|
|
| ||
Feature | Default | Other Options | ||
|
|
| ||
CONNECTED | N (Not connected) | Y (Connected) | ||
LABEL |
| ZONE 1 | Any name (up to eight characters) | |
UNITS |
| FT (feet) | M (meters) | |
AUTO CALIBRATE | Automatically calculates cable length | Allows adjustment to calculated length of cable | ||
|
|
| ||
SENSITIVITY FOR | 150 UA | Can define between 25µA and 300µA | ||
WATER DETECT | ||||
|
| |||
SENSITIVITY FOR | 50 UA | Can define between 20µA and 300µA | ||
CONTAMINATED | ||||
|
|
25