6.8.3Factory Defaults

System and Control Options

6.8.2Change Date & Time/Automatic Daylight Saving Time

The Liqui-tect panel has a built-in, real-time clock that is backed up by an encapsulated lithium bat- tery and set up to adjust automatically for daylight saving time twice a year. The Setup System Info menu allows you to change the date or time or automatic adjustment at any time.

To change the daylight saving time setting, date or time:

• From the Setup System Info Menu, use the arrows ↑↓ to choose Change Date & Time, then press Enter .

• To change the daylight saving time setting:

• To the right of Daylight Svg Time? use the arrows ↑↓ to choose Y (Yes - automatically adjust for daylight saving time) or N (No), then press Enter .

The format of the date and time is DD-MMM-YY HR:MM:SS. To change the date or time:

Press Enter to advance to the next character position you want to change.

Use the arrows ↑↓ to choose from available entries:

Date

Day (DD)

0-31

 

Month (MMM)

JAN-DEC

 

Year (YY)

00-99

Time

Hour (HR)

00-23

 

Minutes (MM)

00-59

 

Seconds (SS)

00-59

Press Enter to advance to the next character position.

When finished, press Enter again.

6.8.3Factory Defaults

Setup System Info Menu

SETUP SYSTEM INFO CHANGE PASSWORD

>CHANGE DATE & TIME

↑↓ =NEXT =SELECT FACTORY DEFAULTS

Change Date & Time

CHANGE DATE & TIME

DAYLIGHT SVG TIME? Y

30-APR-03 10:56:30 ↑↓ =SELECT =NEXT/END

Setup System Info Menu

At any time, you may restore all default values for settings in the Liqui-tect panel as it was shipped, as shown in Table 12.

The password is the sole exception when reverting to the factory default settings. The password can be reset to the factory default of

AAAAonly through the DIP switches. For details, see Change Password on page 35.

Table 12 Factory default settings

 

Feature

Default

Zones

CONNECTED

N (Not connected)

1 & 2

 

 

LABEL

ZONE 1

 

 

UNITS

FT (feet)

 

AUTO CALIBRATE

Automatic

 

SENSITIVITY FOR

150 UA

 

WATER DETECT

 

 

 

SENSITIVITY FOR

50 UA

 

CONTAMINATED

 

 

Alarm

LONGEST CABLE LENGTH

0-1000 ft. (0-304.8m)

outputs

 

 

LEAK & FAULT RELAYS:

NO (Normally Open)

 

NORMALLY OPEN/CLOSED

 

 

 

LEAK & FAULT ALARM:

Y (Latched)

 

LATCHED/UNLATCHED

 

 

Mapping

Current

0UA, where UA represents µA

values

or microAmps

 

 

Distance

(none)

Re-alarm

Delay in minutes

5 minutes

delay

 

 

SETUP SYSTEM INFO CHANGE PASSWORD CHANGE DATE & TIME ↑↓ =NEXT =SELECT

> FACTORY DEFAULTS

Factory Defaults

RESTORE ALL DEFAULTS ARE YOU SURE? Y

↑↓ =Y/N

=END