6.5Setup System - Setup Alarm Outputs

System and Control Options

6.5Setup System - Setup Alarm Outputs

The Liqui-tect panel has six alarm outputs—three types for each zone:

Digital alarm output for cable break detection - a change in state indicates a broken cable or con- tamination on the cable

Digital alarm output for leak detection - a change in state indicates a leak on the cable

Analog alarm output for 4-20mA - the signal may indicate normal operation, the location of a leak, a cable break or contamination

These outputs may have a wide variety of Liebert or other manufacturers’ equipment connected to receive alarm notification.

To configure all alarm outputs:

Log In and Choose Setup System

• From the Main Menu, use the arrows ↑↓ to choose System and Control, then press Enter (see 6.1 - Login for help).

• Enter your password at the Login screen.

• From the System and Control Menu, use the arrows ↑↓ to choose Setup System, then press Enter .

Select Setup Alarm Outputs

• From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Alarm Outputs and press Enter .

Table 9 shows alarm output features and their default settings: you may specify the maximum cable length of analog alarm outputs, define digital alarm output relays as Normally Open or Closed, and set up alarms as Latched or Unlatched.

To change the default settings, use the steps following Table 9.

Table 9

Default settings - alarm outputs

 

 

 

 

 

 

Feature

Default

Other Options

 

 

 

LONGEST CABLE LENGTH

0-1000 ft. (0-304.8m)

Up to 5000 ft. (1524m)

LEAK & FAULT RELAYS:

NO (Normally Open)

NC (Normally Closed)

NORMALLY OPEN/CLOSED

LEAK & FAULT ALARM:

Y (Latched)

N (Unlatched)

LATCHED/UNLATCHED

 

 

Setup System Menu

SETUP ZN1 ZONE 1

SETUP ZN2 ZONE 2

>SETUP ALARM OUTPUTS

↑↓ =NEXT =SELECT

SETUP REALARM DELAY SETUP MAPMODE SETUP SYSTEM INFO

Maximum Cable Length

SELECT LONGEST

CABLE CONNECTED

> 0-500FT

(0-152.4 M)

↑↓ =NEXT

=SELECT

0-1000FT (0-304.8M)

0-1500FT (0-472.2M)

0-2000FT (0-609.6M)

0-2500FT (0-762.0M)

0-3000FT (0-914.4M)

0-4000FT(0-1219.2M)

0-5000FT(0-1524.0M)

Normally Open / Closed

ARE LEAK

& FAULT

RELAYS NORMAL OPEN

OR NORMAL CLOSED? NO

↑↓ =NO/NC

 

 

=END

 

 

 

 

 

 

 

 

Latched / Unlatched

IS LEAK & FAULT ALARM LATCHED? Y

↑↓ =Y/N

=END