Emerson MC68HC16Z1 6.9Reset Latched Alarms, Log In and Choose Reset Latched Alarm, Main Menu

Models: MC68HC16Z1

1 48
Download 48 pages 13.14 Kb
Page 41
Image 41
6.9Reset Latched Alarms

System and Control Options

6.9Reset Latched Alarms

The Reset Latched Alarms menu allows you to clear any leak or fault alarms that have been defined as latched.

To clear latched alarms:

Log In and Choose Reset Latched Alarm

• From the Main Menu, use the arrows ↑↓ to choose System and Control, then press Enter (see 6.1 - Login for help).

• Enter your password at the Login screen.

• From the System and Control Menu, use the arrows ↑↓ to choose Reset Latched Alarm, then press Enter .

Choose Y to Reset Alarms

• From the Reset Latched Alarms Menu, use the arrows ↑↓ to choose Y (Yes - reset all latched alarms) or N (No - do not reset alarms).

(If no alarms have been set up as latched, the screen displays a message, as shown below right.)

• Press Enter .

This is the only way to reset latched alarms. This step is required to return latched points to their normal state. (To set up digital alarm outputs as latched, see 6.5.3 - Define Alarms as Latched or Unlatched.)

Main Menu

VIEW STATUS

> SYSTEM AND CONTROL

↑↓ =NEXT

=SELECT

Login

LOGIN

AAAA

↑↓ =SELECT =NEXT/END

System & Control Menu

SETUP SYSTEM

>RESET LATCHED ALARM

CLEAR ALARM HISTORY ↑↓ =NEXT =SELECT

CLEAR ZONE TREND

Reset Latched Alarms

RESET LEAK & FAULT LATCHED ALARMS? Y

↑↓ =Y/N

=END

Message if No Latched Alarms

ALARMS ARE NOT SET FOR LATCHING

ESC=EXIT

37

Page 41
Image 41