6.4Setup System - Setup ZN2 Zone 2

System and Control Options

6.4Setup System - Setup ZN2 Zone 2

NOTE

The setup options are identical for both zones, except the name of the zone differs.

The Liqui-tect panel has two independent zones—ZN1 and ZN2—that may be configured individually. Each zone can monitor up to 5,000 ft. (1524m) of leak detection cable.

To configure the second zone:

In the Setup System Menu, choose Setup ZN2 Zone 2 (see above right).

Follow the same procedures used in setting up Zone 1, as described in the previous section, 6.3 - Setup System - Setup ZN1 Zone 1.

Setup System Menu

SETUP ZN1 ZONE 1

>SETUP ZN2 ZONE 2

SETUP ALARM OUTPUTS ↑↓ =NEXT =SELECT

SETUP REALARM DELAY SETUP MAPMODE SETUP SYSTEM INFO

Setup Zone 2 Menu

SETUP ZN2 ZONE 2

>CONNECTED: N

LABEL: ZONE 2

↑↓ =NEXT =SELECT

UNITS: FT

AUTO CALIBRATE WATER DETECT:150 UA CONTAMINATED:050 UA