Input Power Connections

Installation

2.4.2Input and Output Power Connections - Large Enclosure

! CAUTION

The 115VAC/230VAC Transformer Module must be connected to a branch circuit with 15A branch circuit protection.

This equipment is intended to be installed by a qualified and certified electrician who must review and approve customer supplied wiring and circuit breakers, verify correct input and grounded connections to ensure compliance with the technical standards and national and local electrical codes.

The Transformer Module shall be used only as indicated by the manufacturer.

! WARNING

Be sure that the power wiring is disconnected from the Liqui-tect panel before installing any wiring to this unit.

Input Power Connections

To connect electrical power to the Transformer Module:

1.

Install electrical wiring from utility power to the Transformer Module.

2.

Use copper wires only; proper wiring to use for power is 14/2 AWG copper wire with ground.

3.

For the TM230 only: strip wires 3/8" (9.6mm).

 

Note: For the TM115, wires are pre-stripped 0.4" (10.2mm) at the factory.

4.

Connect the wiring as follows:

 

 

 

 

 

 

 

 

 

TM115

TM230

 

Connection Type

 

 

White wire

Neutral (L2)

 

Neutral

 

 

Black wire

Line (L1)

 

Power (Line)

 

 

Green wire

Ground lead

 

Ground

 

5.

Secure the incoming electrical service wires to the TM115 input wires with wire nuts as shown in

 

Figure 6 or to the TM230 connectors as shown in Figure 7.

24 VAC Output Power Connections

To connect to the 24VAC outputs:

1.Install electrical wiring from device requiring 24VAC power to the Transformer Module.

2.Use copper wire only; proper wiring to use for power is 18, 20 or 22 AWG copper wire. Strip wire 1/4".

3.There are two 24 VAC output connectors (TB1 and TB2). Terminate wires to the connector as shown in Figures 6 and 7. TB1 and TB2 are NOT polarity sensitive.

4.Secure the wires to the connector.

Figure 6 Power wiring to TM115

Figure 7 Power wiring to TM230

TM115

TM230

Wire nuts connecting electrical wiring

Knockout for

Knockout for

external wiring

external wiring

Ground

Ground

Neutral

Line (L1)

(L2)

 

24VAC output

24VAC output

(TB1)

(TB1)

Troubleshooting - Transformer Module

A common problem and possible solution are shown in the table below. For further information or if you have other problems with the unit, consult your local dealer, Liebert representative or the Liebert Worldwide Support Group.

Problem

Possible Solution

Replacement Fuse Part Numbers

24VAC power not available

Check fuse for respective

• LITTLEFUSE 218002

from TB1 or TB2

output (TB1 or TB2).

• BUSSMANN GDC-2A

11