View Status Options
5.2View Alarm History
The Alarm History Log contains up to 100 records of alarms that have occurred. Records are added to this log as alarms occur.
To view the Alarm History Log:
• From the Main Menu, use the arrows ↑↓ to choose View Status, then press Enter ↵.
• From the View Status Menu, use the arrows ↑↓ to choose View Alarm History, then press Enter ↵ .
5.2.1Alarm History Log
The Alarm History Log screen displays up to 100 records showing alarms generated from the cable, panel operations, return from alarm and loss of power. If the log contains any alarm records, the Alarm His- tory Log screen displays details for each alarm:
•the source of the alarm (for example, ZONE 1 or ZONE 2)
•a brief description of the problem (CABLE OK)
•the date and time the alarm occurred
Main Menu
>VIEW STATUS SYSTEM AND CONTROL
↑↓ =NEXT | ↵ =SELECT |
View Status Menu
VIEW CABLE STATUS
> VIEW ALARM HISTORY
VIEW ZONE TREND | |
↑↓ =NEXT | ↵ =SELECT |
Alarm History Log
>ALARM RECORD 01/100 ZONE 1
CABLE OK
Table 6 shows conditions that the alarm history log records for analog inputs and the panel itself.
Table 6 | Alarm History Log conditions |
| |
|
|
|
|
Source |
| Cable Input | Panel |
CONDITIONS | CABLE BREAK | LOSS OF POWER | |
RECORDED | LEAK DETECTED (& location, e.g., LEAK @ 99 FT) | ALARM SILENCED | |
|
| CONTAMINATED (& location, e.g., CONTAM @ 44 FT) | H/W RESET |
|
| NO LEAK | ALARM RESET |
|
| CABLE OK |
|
If there are no alarms in the log, the screen displays the message:
HISTORY LOG EMPTY
Viewing Additional Screens
There may be up to 100 records of alarm data.
•To view additional records, use the arrows ↑↓ .
•To return to the previous screen, press the ESC key.
21