3.2SPECIFICATIONS--MSM400
Housing | ABS with polycarbonate lid, IP65 | ||
External dimensions | 256.5 wide, 236.7 high, 95.0 deep, including wall mounting brackets | ||
Cable Glands | 3x 16mm | holes and plastic glands supplied | |
| 3x 20mm | holes and plastic glands supplied | |
Weight | 2 kg |
|
|
Wall Mounting holes | 6 off Diam 5.0mm | (See Drawing Section 4.5) | |
Power supply options | 115 V a.c. (±15%) | 50 / 60 Hz | |
| 230 V a.c. (±15%) | 50 / 60 Hz | |
| or 24 V d.c. (15 to 30 Volts) | ||
Power consumption | a.c. 10VA |
|
|
| d.c. 6W |
|
|
Fuse (F1) | 200 mA (T) 5 x 20mm | ||
Current Output | |||
|
|
| maximum load 1KΩ (at 22mA) |
|
|
| maximum applied voltage 48v d.c |
HART | HART digital communications, Two HART internal test terminals provided. | ||
Relay Outputs | 2x SPCO Relays, rated 5 Amps at 250 V a.c. Resistive | ||
DC Power Output | 24V DC for external | sensors such as Mobrey Electrosensor | |
Sensor connections | Terminals for Mobrey sensor Tx and Rx cables, each 2 cores and screen | ||
Trigger inputs | Unit accepts two 5V d.c.trigger input signals. 5V d.c. provided - compatible | ||
| with Mobrey Electrosensor | ||
Terminals | Max. cable size 2.5mm2 | ||
Ambient temperature |
| ||
Max Altitude | 2000m |
|
|
Max Humidity | 95% RH |
|
|
Electrical Safety | Conforms to | ||
Installation Category | Cat III 132V a.c. Max., Cat II 264V a.c. Max. | ||
Pollution Degree | 2 |
|
|
EMC | Complies with EN61326 (Industrial level) |
IP258
10