4.6ELECTRICAL CONNECTIONS
All field wiring connections are accessible by removing the lower lid, which is secured by two screws. Note that it is the responsibility of the installer to observe all local regulations and approval requirements, and to use cable to suit the environmental requirements of the particular application. Obtain and check any hazardous area work permits required before applying power to the MSM400.
The diagram below shows the layout of external connection terminals: all terminal blocks are suitable for wires 0.5mm2 to 2.5mm2
Ensure wiring is suitable for the load current and the insulation is suitable for the voltage, temperature and environment of the installation.
Note that in intrinsically safe systems, apparatus connected to the MSM400 must not be supplied from a voltage greater than 250V rms or 250V DC.
FUSE 200mA
K7941
Figure 9: Connection Terminal Layout
Note that not all of the labelled terminals are functional in this version of the MSM400. The functions available are listed below :
CONNECTION DESCRIPTIONS :
Terminal | Label | Function |
|
| |
1 | RX | A | Sensor Cable |
|
|
2 | RX | B | Sensor Cable |
|
|
3 | RX | SCN | Screen for 1+2 |
|
|
4 | TX | SCN | Screen for 5+6 |
|
|
5 | TX | A | Sensor Cable |
|
|
6 | TX | B | Sensor Cable |
|
|
7 | TRIGGER 0V | Ground ref for Trigger inputs |
| ||
8 | TRIGGER D1 | Digital input No 1 |
|
| |
10 | TRIGGER 5V | 5 V output |
|
| |
16 | I out Io | Current output |
| ||
17 | I out 0V | Current output zero ref terminal |
| ||
18 | I out 24V | Current output 24 V DC loop power : refer to Fig. 10 | |||
RELAY 1 | terminals for Relay 1 |
| |||
RELAY 2 | terminals for Relay 2 |
| |||
25 | DC out 24V | Output of 24 VDC for powering external devices. | |||
26 | DC out 0V | Ref for DC output |
|
| |
27 | DC in 24V | Positive supply at 24VDC to the | |||
28 | DC in 0V | Ref terminal for DC supply input |
| ||
29 | Mains L | AC power input 115/230V, Live terminal | NB: SELECT 115 or 230V | ||
30 | Mains N | AC power input 115/230V, Neural terminal | ON SWITCH ABOVE | ||
31 | Mains E | Protective Earth (PE) |
| THESE TERMINALS |
NOTE 1 The sensors are symmetrical, so either of the two cable pairs can be chosen as "Tx" or "Rx
IP258